background image

 

 

Elektroniksystem i Umeå AB Industrivägen 12, 90130 Umeå, Sweden 

E-mail

[email protected]

 

ǀ

 Web: 

www.elsys.se

 
 

Specifications in this document are subject to change without notice.  

©Elektroniksystem i Umeå AB 2020

 

 

 

www.ime.de

Содержание 110480

Страница 1: ...niksystem i Umeå AB Industrivägen 12 90130 Umeå Sweden E mail support elsys se ǀ Web www elsys se Specifications in this document are subject to change without notice Elektroniksystem i Umeå AB 2020 www ime de ...

Страница 2: ... if it is not to be used for an extended period Otherwise the battery might leak and damage the device Never leave a discharged battery in the battery compartment The device must never be subjected to shocks or impacts To clean the device wipe with a soft moistened cloth Use another soft dry cloth to wipe dry Do not use any detergent or alcohol to clean the device Disposal note in accordance with ...

Страница 3: ...red analog input 0 10V 9 Switch Input Pull up 9 Pulse count Pull up 10 Pulse count Pull down 10 Pulse count Pull down External pulse 11 Pulse count Pull up S0 input 11 4 20 mA input 12 Water leak input 12 Maxbotix distance sensor input 13 Meter Decagon sensor input 13 Pulse count Pull up 2 channels 14 Pulse count Pull down 2 channels 14 Switch input Temperature sensor 15 Sensor configuration 16 NF...

Страница 4: ...l support elsys se ǀ Web www elsys se NFC Read Write 17 Sensor startup 18 Sampling mode Periodic measurement 19 Schedule Transmission 19 External sensors 20 Specifications 21 Sensor payload format 21 Regulations 22 Legal Notices 22 Declaration of conformity 22 www ime de ...

Страница 5: ...her with electricity meters flow meters analog sensors moisture sensors and other external sensors ELT 2 is enclosed in an IP67 box and have four internal sensors temperature sensor humidity sensor accelerometer and an atmospheric pressure sensor This is a battery powered device equipped with NFC Near Field Communication and can easily be configured from a smartphone The barcode contains DevEUI an...

Страница 6: ...ure Detects acceleration Analog 0 10 V input Digital input Direct connection to various external sensors and equipment Easy installation Easy configuration IP67 Classified Battery powered Long range communication Configurable over NFC Configurable over the air Ten years of battery life Supported channel plans US902 928 EU863 870 AS923 AU915 928 KR920 923 RU864 IN865 HK923 CE Approved and RoHS comp...

Страница 7: ...thium Battery ER14505 Caution Using batteries other than the ones provided may result in loss of performance and battery life and also damage to the device Dispose of properly observing environmental protection rules 3 Connect any eventual external sensors 4 Close the lid and tighten the screws carefully Make sure that the cable gland and antenna connection is tightened to prevent ingress of moist...

Страница 8: ...r 1 wire interface Connect a DS18B20 compatible sensor Select Temperature sensor 1 wire in the application Sensor Settings ELT input is internally pulled up by 2 2kΩ Analog input 0 3 or 0 10 Voltage Input signal between input and ground Select Analog input 0 3V or Analog input 0 10V in the application Sensor Settings ELT input is internally pulled down 0 10V 0 10V www ime de ...

Страница 9: ... application Sensor Settings Select Eternal startup time and configure ON time for sensor External startup time is how long the sensor will be powered before sampling value ELT input is internally pulled down and the input impedance is 7 4 kΩ Switch Input Pull up Input signal between input and ground Select Switch Normally open in the application Sensor Settings ELT input is internally pulled up b...

Страница 10: ...d Select Pulse input pull up in the application Sensor Settings ELT input is internally pulled up by 50 k Ω Pulse count Pull down Input signal between input and B Select External startup time in the application Sensor Settings and configure ON time for always on that is 1000000ms Select Pulse input pull down ELT input is internally pulled down by 50 kΩ www ime de ...

Страница 11: ... signal between input and GND Pulse signal from 3 to 12 voltage Select Pulse input pull down in the application Sensor Settings ELT input is internally pulled down by 50 kΩ Pulse count Pull up S0 input S0 signal between input and ground Select Pulse input pull up in the application Sensor Settings ELT input is internally pulled up by 50 kΩ www ime de ...

Страница 12: ...the application Sensor Settings Connect resistor parallel to the input Value of R can be calculated as 𝑈 𝑅 𝐼 For full range use 536Ω resistor 20mA will then read as 10V Water leak input Connect water leak cable sensor or open ends to IO2 and IN Select Water leak in the application Sensor Settings Range 0 255 depending on conductivity www ime de ...

Страница 13: ...ect Maxbotix in the application Sensor Settings Use the same settings for the ELT Ultrasonic Meter Decagon sensor input Connect the Meter Decagon sensor according to the diagram In the application Sensor settings please follow these instructions For Teros 10 ECH2O 10HS and ECH2O EC 5 select Meter Soil sensor analog For Teros 11 Teros 12 and ECH2O 5TE select Meter Soil sensor digital www ime de ...

Страница 14: ...nd Select Pulse input pull up in the application Sensor Settings ELT input is internally pulled up by 50 kΩ Pulse count Pull down 2 channels Input signal between input IO2 and B Select External startup time in the application Sensor Settings and configure ON time for always on that is 1000000ms Select Pulse input pull down ELT input is internally pulled down by 50 kΩ www ime de ...

Страница 15: ...w elsys se Switch input Temperature sensor Connect a DS18B20 compatible sensor according to the diagram Connect a limit switch door switch reed switch etc between IO2 and GND Select Temperature sensor Switch in application Sensor Settings ELT input is internally pulled up by 50 kΩ on IO2 www ime de ...

Страница 16: ...on 1 Download ELSYS Sensor Settings application from Google Play or App Store from iOS 13 and install it on a smartphone or tablet The device must support NFC 2 Enable NFC on the device and start the application 3 Place your device on top of the NFC antenna on the sensor 4 Remove the device Current settings will be displayed in the application 5 Use the application to change any settings if needed...

Страница 17: ...FC configuration data to the sensor it starts a timer and delays its action 5 seconds 2 After the delay the sensor determines if the NFC data has changed or not If the data has changed the sensor reboots and starts from power up 3 Write your settings in the application and then locate the NFC antenna of the phone and sensor Keep the two devices close and don t move them to get the best connectivit...

Страница 18: ...C chip when something changes in the sensor or if NFC data is corrupted by an NFC writer or phone The sensor always writes the new configuration to NFC chip at startup 3 When the configuration is done the sensor tries to join the network if OTAA Over the Air Activation is enabled 4 The sensor LED flashes orange when it tries to join a network It will try to join every 10 seconds initially This int...

Страница 19: ...Sweden E mail support elsys se ǀ Web www elsys se Sampling mode Periodic measurement The sensor makes periodic measurements according to the user configurations Schedule Transmission The sensor transmits the data according to the user configurations www ime de ...

Страница 20: ...ww elsys se External sensors The sensor makes periodic measurements according to the user configurations External sensors may have additional startup time Configure the External startup time according to this For best performance use a cable as short as possible to your external sensor www ime de ...

Страница 21: ...d US902 928 EU863 870 AS923 AU915 928 KR920 923 RU864 IN865 HK923 Range 8 km Operating conditions 40 C 60 C 40 C 85 C External power supply 0 100 RH 260 1260 hPa Temperature range 40 125 C Temperature resolution 0 05 C Temperature accuracy 0 3 C Humidity range 0 100 Humidity resolution 0 05 RH Humidity accuracy 2 RH Pressure accuracy 1 hPa Pressure range 260 1260 hPa Dimensions 94 x 59 x 35 mm Bat...

Страница 22: ...oniksystem i Umeå AB reserves all rights to revise or update its products software or documentation without any obligation to notify any individual or entity ELSYS and ELSYS logo are trademarks of Elektroniksystem i Umeå AB All other brands and product names referred to herein are trademarks of their respective holders Declaration of conformity Hereby Elektroniksystem i Umeå AB declares that ELT 2...

Отзывы: