Checking the usage

VFC

The linear flow control is designed to adjust volumes 

of gas and cold air on various appliances. The VFC 
with actuator IC 20/IC 30/IC 40 (IFC) is suitable for 
regulating flow rates for control ratios up to 25:1 
in modulating or stage-controlled combustion pro-
cesses.
Linear flow control VFC and actuator IC 20 or IC 40 
can be supplied separately or assembled. IC 30 is 
supplied separately.

This function is only guaranteed when used within 

the specified limits – see also page 5 (Technical 
data). Any other use is consider
ed as non-compliant.

Type code

Code

 Description

VFC

IFC

Linear flow control

Linear flow control with actuator

 

Size 1 

Size 3

T

T-product

0 
5 

0 
5 

40 

50 
65 

-

Inlet flange: DN 10 (

3

/

8

") 

DN 15 (½") 
DN 20 (¾") 

DN 25 (1") 

DN 40 (1½") 

DN 50 (2") 

DN 65 (2

½

") 

no inlet flange

/0 
/5 
/0 
/5 
/40 
/50 
/65 
/-

Outlet flange: DN 10 (

3

/

8

") 

DN 15 (½") 
DN 20 (¾") 

DN 25 (1") 

DN 40 (1½") 

DN 50 (2") 

DN 65 (2

½

") 

no outlet flange



F

Rp internal thread 

NPT internal thread 

ISO flange

05

p

u max.

 500 mbar

-08 
-5 
-0 
-5 
- 
-40

Cylinder size

P
M


4

-

Accessories, right, inlet

Plug

Pressure test point

Pressure switch for gas DG 17VC
Pressure switch for gas DG 40VC

Pressure switch for gas DG 110VC
Pressure switch for gas DG 300VC

No accessories

Code

 Description

P
M

-
-
-
-4
-

Accessories, right, outlet

Plug

Pressure test point

Pressure switch for gas DG 17VC
Pressure switch for gas DG 40VC

Pressure switch for gas DG 110VC
Pressure switch for gas DG 300VC

No accessories

The same accessories can be selected for the left- 

or right-hand side.

/0
/40

Actuator IC 20
Actuator IC 40

-07
-5
-0
-60

Running time [s]/90°: 

7.5

15

30
60

W
Q
A

Mains voltage:  

230 V AC, 50/60 Hz
120 V AC, 50/60 Hz

100 – 230 V AC, 50/60 Hz


Torque:

2.5 Nm

3 Nm

T

D

A

Three-point step control

0 (4) – 20 mA, 0 – 10 V 

continuous control

Digital input

4 – 20 mA analogue input

R0 

1000 Ohm feedback  

potentiometer

no speci-
fication 

-I

Mounting actuator with electrical 

 connection: 

outlet side 

 

inlet side

VFC part designations

1

2

3

  Test point for inlet pressure p

u

  Test point for outlet pressure p

d

  Adjusting spindle

Содержание Kromschroder Linear flow control VFC

Страница 1: ...ON Indicates possible material damage All interventions may only be carried out by qualified gas technicians Electrical interventions may only be carried out by qualified electricians Conversion spare parts All technical changes are prohibited Only use OEM spare parts Changes to edition 10 15 The following chapters have been changed Checking the usage Installation Technical data Contents Operating...

Страница 2: ...l thread NPT internal thread ISO flange 05 pu max 500 mbar 08 15 20 25 32 40 Cylinder size P M 1 2 3 4 Accessories right inlet Plug Pressure test point Pressure switch for gas DG 17VC Pressure switch for gas DG 40VC Pressure switch for gas DG 110VC Pressure switch for gas DG 300VC No accessories Code Description P M 1 2 3 4 Accessories right outlet Plug Pressure test point Pressure switch for gas ...

Страница 3: ...nstallation location must be dry Do not install the unit in the open air Use approved sealing material only Install the VFC in the pipe free of mechanical stress Do not clamp the unit in a vice or use it as a lever Only secure the flange by holding the octagon with a suitable spanner Risk of external leakage Installation position for IFC 20 and IFC 40 vertical or horizontal never upside down Insta...

Страница 4: ... for gas downstream of the VFC 5 Once the tightness test has been carried out successfully move the VFC to the closed posi tion once more using the actuator IC Pipeline leaking replace O ring on flange see page 5 Seal set for sizes 1 and 3 Then check for tightness once again Unit leaking remove the unit and return it to the manufacturer Setting the flow rate CAUTION When setting a higher flow rate...

Страница 5: ...ous biogas max 0 1 by vol H2S or clean air other types of gas on request The gas must be dry in all temperature conditions and must not contain condensate Control ratio 25 1 Leakage rate 2 of kVS value Max inlet pressure pu max 500 mbar 7 25 psi Running times IC 20 7 5 s 15 s 30 s 60 s IC 30 30 s 60 s IC 40 4 5 s 76 5 s Connection flanges Rp internal thread pursuant to ISO 7 1 Housing material alu...

Страница 6: ...Declaration of conformity We the manufacturer hereby declare that the product VFC marked with product ID No CE 0063CO1153 complies with the essential requirements of the fol lowing Directives and Standards Directives 2009 142 EC Standards EN 13611 The relevant product corresponds to the type tested by the notified body 0063 The production is subject to the surveillance proce dure pursuant to Direc...

Отзывы: