EK280
Application Manual
35
6.2
NF pulse output (low-frequency)
Each of the outputs 1 to 4 (terminals DA1 to DA4) can be programmed as a low-frequency pulse output.
6.2.1
Parameterization
Parameterization is carried out via the keyboard on the EK280.
Alternatively, parametrization can be carried out using the
enSuite
program. The paths which are subsequently
described can be found in
enSuite
under "
Parameterize online
" > "
Parameters
".
Setting up the output mode:
Move the cursor to register "
Serv.
"and along the following path to the mode for the corresponding
output
"Md.O1"
to
"Md.O4"
:
Serv.
Outputs
Output 1
Md.O1
Serv.
Outputs
Output 2
Md.O2
Serv.
Outputs
Output 3
Md.O3
Serv.
Outputs
Output 4
Md.O4
i
The low-frequency pulse output of the EK280 can be operated with active or inactive logic. The
output mode must be programmed accordingly for this purpose (see below).
Press the ENTER
button. The actual parameterized value flashes.
Press one of the arrow buttons
or
until the
"pulse+"
(Logic active) or
"pulse -"
(Logic inactive)
text flashes.
Press the ENTER button to confirm the value setting. Input can be canceled using the ESC key.
Setting up the source for the output:
When in the corresponding menu press the
button until
"Sc.O1
",
"
Sc.O2
",
"
Sc.O3
", or
"
Sc.O4
" is
displayed.
Press the ENTER
button. The actual parameterized value flashes.
Move the cursor to the digits using the
or
arrow keys and update them using the
or
arrow
keys to a value specified in the table.
Sc.O…
Description
02:300_0
Vb
Volume at base conditions (undisturbed)
02:301_0
VbD
Volume at base conditions (disturbed)
02:302_0
VbT Volume at base conditions total (undis disturbed)
04:300_0
Vm
Volume at measurement conditions (undisturbed)
04:301_0
VmD
Volume at measurement conditions (disturbed)
04:302_0
VmT Volume at measurement conditions total (undis disturbed)
Press the ENTER button to confirm the value setting. Input can be canceled using the ESC key.
Setting up the cp value for the output:
i
The cp value of an output states how many pulses were emitted per cubic meter. A cp value
of 0.1/m3 (0.1 pulses per m3) means that e.g. a pulse is emitted per 10m3.
When in the corresponding menu press the
button until "
cp.O1
", "
cp.O2
", "
cp.O3
" or "
cp.O4
" is
displayed.
Press the ENTER
button. The actual parameterized value flashes.
Move the cursor to the digits using the
or
arrow keys and update them using the
or
arrow
keys to the desired cp value for the corresponding output.
Press the ENTER button to confirm the set value. It is possible to abort the entry by pressing the
ESC button.