EK280
Application Manual
117
7.5.2
Point-in-time connection
The major parameters for activating a point in time connection are listed below.
To do so, in the enSuite program, change the sub menu "
Connections"
> "
Connection 7 or 8
".
Point-in-
time
connection
Meaning
Protocol-
Type
TypePr
0 = Server (not to be used for point in time connections)
3 = DLMS (the connection to the target is a DLMS connection)
4 = Modbus-Master (the connection to the target is a Modbus connection)
5 = IEC1107 (the connection to the target is a IEC-1107 connection)
6 = EIServer (the target is an EI server)
cycle
Cycle of a regular point in time connection (e.g. hourly, daily, weekly, monthly)
CTim1
Start of a point in time connection (e.g. daily at 6:00 AM, or another time)
Destn
0 = no conn. (Connection is inactive)
1 = Dest 1 or 2 (a connection to target 1 is being constructed or if a fault occurs, to
target 2 instead)
2 = Dest 1 and 2 (a connection to target 1 and target 2 is being constructed)
Dst 1, 2
Reference to a number in the telephone book, the recipient of this telephone book entry
will be called by the EK280.
Iface
2 = Terminal / ext. Modem
3 = internal modem
SuplT
Type of power supply as a condition for the connection
1 = always
2 = Battery
3 = ext. supply
StCon
Current status of this connection
SDst 1, 2
Current status of communication with the target
TestC
The function for the point in time connection can be triggered at any time (e.g. for testing
purposes)
Use the enSuite program and change over to the sub-menu "
Telephone book
" > "
Receiver 1 - 10
"
Telephone
book
Definition
TelNo
Recipient's telephone number. If a GSM modem is in use, then this number will be
called.
Serv.
Server TCP/IP address. If a GPRS modem is in use then an attempt is made to
reach this IP address, and if no IP address has been parameterized then
alternatively an attempt is made to call the telephone number.
Port
Server port number. If a GPRS modem is in use then an IP connection is started
off via this port.
Name
Name of recipient.
A point in time connection can be manually initiated at any time (e.g. for a test). To do so, change the
parameter "TestC" to 1 ("open"). The EK280 opens the interface and attempts to reach the target.
In order to follow the progress of the point in time connection, observe the "StCon" parameter and "SDst 1,
2".
Use the enSuite button "
Refresh
”
at the menu bar of enSuite, to get the actual information in the enSuite.
If the conditions for regular activation of the point in time connection are met, then the interface is opened and
the EK280 attempts to reach the target.
Conditions for regular activation of the point in time connection are as follows: