BCU 580 · Edition 11.15
98
12 Project planning information
12 .1 Installation
Installation position as required.
The BCU mounting is designed for horizontally aligned
35 × 7.5 mm DIN rails.
If the DIN rail is aligned vertically, end clamps are required (e.g.
Clipfix 35 by Phoenix Contact) to prevent the BCU from slipping.
Environment
Install in a clean environment (e.g. a control cabinet) with an
enclosure ≥ IP 54, whereby no condensation is permitted.
12 .2 Commissioning
Do not start the BCU until the parameter settings and wiring
are correct and the faultless processing of all input and output
signals complies with the local standards.