30
Installation
, connection and commissioning
5.3.1.1 Opening the calibration lock
On circuit board in the housing floor, the calibration lock can be found in the form of a key
that can be secured with an adhesive label. This needs to be operated to change relevant
values and parameters.
Ill.: 13
Position of the key for
opening the calibration
lock.
5.3.1.2 Setting parameters for the NF pulse transducer of the gas meter
If a low-frequency pulse transducer is connected in accordance with 5.2.1.1, you can set the
input mode and cp value as follows:
1. Setting the input mode:
Move the cursor to the "Serv" tab and via the following path to the value "Md.I1" input
mode:
Serv.
Inputs
Input 1
Md.I1
Press the key combination ENTER
+
The value set flashes.
Repeatedly press one of the
or
arrow buttons until the text "Pulse input" flashes.
Press the ENTER
+
button to confirm the set value. It is possible to abort the
entry by pressing the key combination ESC
+
.
2. Setting the cp value (pulse constant):
Move the cursor to cp value "cp.I1" in the same path
Press the key combination ENTER
+
One digit of the value flashes.
Move the cursor with the arrow buttons
or
to the digits and change these with the
arrow buttons
or
.
Press the ENTER
+
button to confirm the set value. It is possible to abort the
entry by pressing the key combination ESC
+
.
5.3.1.3 Setting the volume at measurement conditions
In order to control the recording of volumes within measurement conditions, the EK205's
counter can be set to the same value as the gas counter once when the administrator lock is
open. Setting the volume is always possible when the calibration lock is open.
Open the administrator lock or the calibration lock
Move the cursor to the "
Serv
" tab and via the following path to the value "
VmA
"
(adjustable volume at measurement conditions) input mode:
Serv.
Volume
Actual volume
Synchronization Vm
VmA
Содержание EK205
Страница 1: ...Operating manual Volume conversion device EK205 ...
Страница 6: ......
Страница 64: ...64 Appendix 9 2 Conformity declarations19 19 IECEx is not available for all device types ...
Страница 65: ...Appendix 65 9 3 Design test certifications 9 3 1 ATEX EC Type Examination Certificat ...
Страница 66: ...66 Appendix ...
Страница 67: ...Appendix 67 ...
Страница 68: ...68 Appendix 9 3 2 IECEx Certificate of Conformity20 20 Not available for all device types ...
Страница 69: ...Appendix 69 ...
Страница 70: ...70 Appendix ...
Страница 71: ...Appendix 71 ...