AHU Electrodes Humidifier - VEH
20.2.EN
13
Elsteam S.r.l - via E. Fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: [email protected] - Web: http://www.elsteam.com
11
Alarms
DISPLAY
Description
Resolution
A L A R M
LACK WATER
No water in the kettle
Check the input solenoid
Check the electrical connections of the solenoid
A L A R M
DRAIN MOTOR
The drain motor is not closed within the
allotted time. (Timeout of closing)
Check the electrical connections of the motor
Check that there are no blocks of limestone or objects
blocking the closure
A L A R M
CLOGGED DRAIN
limestone blocks draining block
Check the amount of scale in the kettle/draining block.
Perform manual cleaning of kettle/draining block