924KTE4.01 - KT
series humidifiers
05/2021
| 13 |
5. INSTALLATION
5.1 Humidifier parts
5.1.1 Top
• Steam outlet;
•
Male3/4"GASconnectorforwatersupply.
5.1.2 Bottom
• Water outlet to connect to sewer system;
• Strain relief cable gland for power supply wiring;
• Strain relief cable gland for wiring of regulation board.
5.2 Water connections
You will need the following components to plumb in the humidifier:
• An intercept tap;
•
Asupplementaryfiltertotheonealreadyinthesolenoidvalve;
• A pressure reducer (if the pressure of the mains water exceeds 1 MPa (10 bar)).
N.B.:
Ifapressurereducerisused,makesureitiseffectiveanddoesnotcauseadrasticreductioninpressurewhenthemains
pressure is very low.
NOTICE
MALFUNCTIONING OF THE EQUIPMENT
• The feed water must have a minimum pressure of 0.2 MPa (2 bar).
• Connect the solenoid valve to the mains using the flexible hose supplied to reduce water hammers in the hose to the
humidifier.
•
Duringinstallation,becarefulnottodamagetheplasticthreadofthesolenoidvalve.
•
Whenmakingthewaterconnections,itmustalwaysbepossibletoaccessthemechanicalfilterinthewaterloadsolenoid
valve for cleaning.
5.2.1 Characteristics of water
• Water pressure between 0.2...1 MPa (2...10 bar);
•
Temperaturebetween1...50°C(33.8...122°F);
•
Conductivitybetween75...1250μS/cm;
• Maximum water hardness between 5...50 °f.
N.B.:
Ifwaterisharderorifthereismoreorganicresidueinit,thehumidifierwillstilloperatecorrectlybutitmustbeserviced
more regularly.
Dos
•
Flushwaterintothedrainforacoupleofhoursbeforemakingthefinalconnection.
•
Checktheconditionoftherubbercouplingregularlytopreventproblemsandwaterleakingintotheroom.
Don’ts
•
Softenthewater.Ifthewaterhardnessisabove50°forifitissuchthattheboilerrequiresregularmaintenance,use
demineralisedwatermixedwithtapwaterinapercentagethatensuresaminimumconductivityof200μS/cmanda
hardness of at least 10 °f.
NOTICE
MALFUNCTIONING OF THE EQUIPMENT
• Do not use softened water.
•
Oncethehumidifierhasbeeninstalled,flushthepipeswiththeremainingwatertopreventblockingthefilter.
•
Checkallthepartsofthehumidifierareintact.
•
Ifevenonepartofthehumidifierisdamaged,suspendinstallation.
5.3 Water discharge system
Asthishumidifierhasanautomaticboilercleaningfunction,thewateroutletmusthaveacapacityofatleast10litresinafew
seconds (maximum 1 l/s).
NOTICE
MALFUNCTIONING OF THE EQUIPMENT
Sizetheoutletpipetopreventobstructionsorblockagesduringtheautomaticcleaningcycle.