background image

 

ems55advanced-TCCC-Troubleshooting-Quick-Guide-Iss4 

Elstat, Astra Business Centre, Roman Way, Preston, Lancashire, PR2 5AP, United Kingdon 

Telephone: +44 (0) 161 22 77 200 

www.elstatgroup.com 

ems55

advanced

 - Troubleshooting 

Quick Guide 

User interface 

 

Note: The motion sensor is integrated with the ems controller 
(ems55

advanced

) or remote (ems55R

advanced

).  

LED indicators 

 

Compressor. 

On when the compressor is 
running. 

 

Fan. 

On when the evaporator fan is 
running. 

 

Saving mode 
temperature 
disable. 

On if the saving mode 
temperature is disabled. 

 

Motion. 

On when motion detected. 

Buttons 

 

Set 

 

Up 

 

Defrost 
(Starts a manual 
defrost) 

 

Down  
(Also cancels alarms) 

Power up sequence 

 

Checks all the display elements 
are working. 

 

Displays the firmware version. 
(Example) 

 

Displays the checksum. 
(Example) 

Normal operation 

During normal operation the EMS will display one of the messages 
below.  If one of the below messages is not displayed the EMS has 
registered and alarm or fault. 

 

Ready mode  
(Displays 

USE

 or temperature) 

 

Saving mode 

 

Defrost mode 

 

Door open 

 

Freeze up protection 
If evaporator frozen, ensure appliance sensor is 
connected properly. Disconnect appliance sensor and 
ensure display shows PF1. Otherwise, replace the 
controller. 

Alarms and troubleshooting 

The EMS controller can display messages to aid fault diagnosis.  If an 
alarm sounds and the EMS controller displays any of the alarms 
below, contact your service provider. 

 

Refrigeration system failure 

 

Condenser high temperature alarm (requires a 
condenser sensor) 

 

Appliance sensor failure 

 

Condenser sensor failure (if used) 

 

Evaporator sensor failure (if used) 

 

Over voltage alarm (SHI) or under voltage alarm 
(SLO), if used.  
Note that the compressor does not run in over or 
under voltage conditions. 
 

 

Door open alarm 

Cooler 
lights do 
not switch 
on 

If EMS controller is in the ready mode, ensure 
that the light switch inside the cooler switched on. 

No power 

Check for 12 to 13VAC at the rear connector of 
the ems controller. 

 