10.27
high voltage (HI)
The table below details the high voltage (
HI
) parameter.
display
description
Defines the maximum voltage allowed before switching off the compressor.
The high voltage (
HI
) values are approximations and not actual voltage readings (see table below).
considerations
1. Must not be used with an external voltage stabiliser
2. Must only be used with an elstat supplied transformer
3. Only used with ems55
advanced
and ems55R
advanced
range
180 to 250 (not Vac)
global default
250 (disabled)
100V line
110-120V line
220-240V line
voltage
HI
voltage
HI
voltage
HI
110
180
139
180
230
190
114
185
142
185
235
195
118
190
145
190
240
200
122
195
148
195
245
205
250
210
255
215
260
220
note: Voltage measurement is accurate to ±10%. 265
225
Caution:
l
High voltage protection is not calibrated and actual performance can be influenced by several factors.
Therefore, total protection cannot be guaranteed.
10.28
condenser high temperature (Ht)
The table below details the condenser high temperature (
Ht
) parameter.
display
description
Defines the maximum temperature measured in the refrigeration system by
monitoring the condenser sensor.
On reaching the condenser high temperature (
Ht
), the ems controller disables
the compressor and activates an alarm.
considerations
1. Is not used with CO2 (R744) coolers.
ems55advanced and ems55Radvanced / General Use
76 of 84