10.24
fan cycle off (FCF)
The table below details the fan cycle off (
FC F
) parameter.
display
description
Defines the inactive period of the evaporator fan while the compressor is switched off.
considerations
Fan cycle is the fan cycle on (
FC O
) time + the fan cycle off (
FC F
) time.
Not used on the ems25
+
range
1 to 30 minutes
global default
1 minute
ems75sz: 20 minutes
10.25
fan cycle on (FCO)
The table below details the fan cycle on (
FC O
) parameter.
display
description
Defines the active period of the evaporator fan while the compressor is switched off.
considerations
Fan cycle is the fan cycle on (
FC O
) time + the fan cycle off (
FC F
) time.
Not used on the ems25
+
range
1 to 30 minutes
global default
30 minutes
ems75sz: 5 minutes
10.26
fan set point (FSP)
The table below details the fan set point (
FS P
) parameter.
display
description
Prevents excessive condensation on the evaporator in environments where warm, and presumed
humid, air is present by operating the evaporator fan.
If the fan set point (
FS P
) temperature is exceeded, the evaporator fan running continuously even if the
door is opened.
On reaching set point (
S P
) temperature, the evaporator fan switches off during door openings.
considerations
Not related to fan cycle on (
FC O
) or fan cycle off (
FC F
).
Not used with OFC firmware or the ems25
+
range
01 to 30ºC (33 to 86ºF)
global default
15ºC (59ºF)
ems55advanced and ems55Radvanced / General Use
75 of 84