display
description
Defines the minimum number of door openings or motion counts to indicate an active 30 minute period
in the self-learning matrix, as described below. The activity frequency applies across all 30 minute peri-
ods within the self-learning matrix, not to individual 30 minute periods.
considerations See below.
range
See below
global default
00 (low frequency)
The table below describes the values for activity frequency (
AF
).
value name
description
00
low frequency
1 door opening or 1 motion count
01
medium frequency
1 door opening or 3 motion counts
02
high frequency
2 door openings or 6 motion counts
03
automatic
The ems controller runs continuously for 48 hours in the
ready mode. After 48 hours, the ems controller sets the
value of the activity frequency to 0, 1, or 2.
Note:
l
If
AF
is set to 3, the ems controller must run continuously for 48 hours to set the value of the activity frequency.
If power is lost during the 48 hour period, the ems controller restarts the 48 hour period.
The ems controller must complete the 48 hour period to determine the activity frequency before starting the 1-day or 7-day learning
period.
10.5
marketing mode (Ar)
The table below details the marketing mode (
Ar
) parameter.
display
description
Sets the cooler lights to remain on at all times for display purposes.
The coolers lights will remain on during
saving mode
.
considerations
Does not affect saving temperature.
Made available to ems55
advanced
GDC firmware from June 2012.
Not used with OFC firmware.
range
00 (off) or 01 (on)
global default
00 (off)
10.6
buzzer enable (b0)
The table below detail the buzzer enable (
b0
) parameter.
ems55advanced and ems55Radvanced / General Use
68 of 84