5.
Set the parameters to the values of the USB serial port of the local computer. For example:
parameter
value
COM port
COM port allocated to the cradle. For example, 3.
Baud rate
9600
Data bits
8
Parity
None
Stop bits
1
Flow control None
6. Click OK.
9.9
how to load the parameter settings
Use the parameter loader to load the parameter settings to the parameter programming tool (dongle) as follows:
1. Extract the ZIP file from the folder which contains the parameter information pack and the parameter settings to a suitable location.
For example, C:\Program Files\elstat.
2. Start the parameter loader as follows:
l
Click Parameter Loader in the Start menu.
l
Double-click the file ParameterLoader.exe.
3.
Insert the parameter programming tool into the docking cradle, as shown below.
4.
Click Load XML and browse to the location of the extracted file and then select the XML file with the parameter set-
tings.
For example, select the XML file C:\Program Files\elstat\EMS25PLUS-GDC-12312-NNNN.xml.
5.
Ensure that the parameter values displayed on the parameter loader are correct, as stated in the parameter inform-
ation pack. The parameter loader also displays the name of the XML name.
6.
Make a note of the appropriate checksums on the parameter loader as detailed in the following table.
l
To help service engineers, mark the appropriate checksum on the identification tag of the parameter programming tool (dongle).
CRC-A
Checksum of the XML file. For elstat reference purposes only.
CRC-B
Checksum displayed on an ems55
advanced
with firmware version E52 F07.
Displayed when rebooting the ems controller following download of the para-
meter settings with the parameter programming tool (dongle).
ems55advanced and ems55Radvanced / General Use
62 of 84