17
Setting the parameters
Cala KNX M-T push button
• Version: 13.09.2019 • Technical changes and errors excepted.
5.4.2. Control modes for drive control
Behaviour on button actuation in standard control mode:
Standard:
If briefly operated, the drive will move incrementally or stops. If operated longer, the
drive will move up to the end position. The time difference between "short" and "long"
is set individually.
Standard inverted:
When pushed shortly, the drive moves up to the end position. When pushed for longer,
the drive moves incrementally or stops. The time difference between "short" and
"long" and the repeat interval is set individually.
Comfort mode:
In the
comfort mode
pushing the button briefly, a bit longer and long will trigger dif-
ferent responses of the drive. The time intervals are set individually.
By pushing the button (shorter than adjustable time 1) the drive will be positioned
(resp. stopped) incrementally.
If the drive is to be moved a bit farther, then a little longer push is needed (longer than
time 1 but shorter than time 1+2). The drive stops immediately when releasing the but-
ton.
If the drive must be moved independently into the end position, the button is released
only after times 1 + 2 have expired. The move can be stopped by briefly pushing.
short:
hold
Blind
Stop/Step
Up or down
Shutters
Stop
Up or down
Awning
Stop
In or out
Windows
Stop
Closed or open
Control mode
Standard
Behavior during button operation:
short = stop/increment long = Up or Down
Time between short and long
in 0.1 seconds
1...50; 10
Control mode
Standard inverted
Behavior during button operation:
short = Up or Down long = Stop/Step
Time between short and long
in 0.1 seconds
1...50; 10
Repeat the step command
for a long button press
every 0.1 s • every 2 sec; every 0.5 sec