4
Commissioning
Sensor KNX T-UP gl
• Version: 05.09.2022 • Technical changes and errors excepted.
•
PI controller for heating
(one or two step) and
cooling
(one or two step)
depending on temperature. Control according to separate target values or
basic target temperature
•
Threshold values
can be adjusted per parameter or via communication
objects: 3 × temperature
•
4 AND and 4 OR logic gates
with each 4 inputs. Every switching incident as
well as 16 logic inputs in the form of communication objects, may be used as
inputs for the logic gates. The output of each gate may optionally be configured
as 1 bit or 2 x 8 bits
•
2 actuating variable comparators
for output of minimum, maximum or
average values. Each with 5 inputs (for values received via communication
objects)
3.
Commissioning
Configuration is made using the KNX software as of ETS 5. The
product file
can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de
in the “Service” menu.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting approx. 6 seconds. During this phase no information can be received or sent via
the bus.
3.1. Addressing the equipment
The equipment is delivered with the bus address 15.15.255. Another address can be
programmed using the ETS.
For this purpose there is a button with a control LED on the unit.