Parameter setting
Weather Station Suntracer KNX sl basic
• Version: 26.08.2021 • Technical changes and errors excepted.
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
6.5.
Frost alarm
If necessary, activate the parameter frost alarm.
Set which conditions are valid for the frost alarm. The frost alarm is active in cold out-
door temperatures in combination with precipitation.
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• Do not send message
• send 0
• send 1
Action upon release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
do not send message •
Status object/s send/s
Switching output sends on change to 1
do not send message •
If switching output = 1
send 1
Switching output sends on change to 0
do not send message •
If switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and
periodically
If switching output = 1
send 1
Switching output sends on change to 0 and
periodically
If switching output = 0
send 0
Use frost alarm
No •
Yes
Start frost alarm when
an external temperature of (in 0.1 °C)
is not reached.
-50 ... 40; 20
during or until (in hours)
after precipitation.
1 ... 10; 5
End frost alarm when
an external temperature of (in 0.1 °C)
30 ... 100; 50
for more than (in hours)
is exceeded.
1 ... 10; 5