Indoor Sensor WG AQS/TH gl

1

Indoor Sensor WG AQS/TH gl

 • Version: 25.11.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

EN

WG AQS/TH gl

Indoor Sensor

Technical specifications and installation instructions

Item number 20559

1.

Description

The 

Indoor Sensor WG AQS/TH gl

 transfers temperature, humidity and CO

2

 con-

tent of the air to the control system via radio. Several separate 

WG AQS/TH gl

 can

be taught to one control system. The teaching is described in the chapter “Learn wi-
reless connections” (manual of the control system).

The 

WG AQS/TH gl

 consists of the housing, the base plate and a frame. As an al-

ternative to the supplied frame, a frame of the switch series used in the building may
be used. You will additionally require a junction box according to DIN 49073 (not in-
cluded in scope of delivery). 

For power supply (11…28 V DC), e. g. 12 V DC can be tapped from the connection
board of the control unit (multifunctional input).

Functions:

Measurement of 

temperature

air humidity

 (relative) and 

CO

2

 content of 

the air

Suitable for: WS1 Color/Style, (KNX) WS1000 Color/Style/Connect, Solexa II 
(Temperature evaluation only)

1.1. Scope of delivery

Housing

Base plate

Frame

You will need

 in addition

 (not supplied):

Device socket according to DIN 49073

1.2. Technical specifications

The product conforms with the provisions of EU guidelines.

1.2.1. Measurement accuracy

Deviations in measured values due to interfering sources (see chapter 

installation

site

) must be corrected in the controller menu in order to achieve the specified sen-

sor accuracy.

To ensure a correct 

CO

2

 measurement

, the device must be installed in a windproof

socket. After applying the operating voltage, it can take up to 15 minutes until the

CO

2

 measured value

 is output correctly.

The 

measured temperature and humidity values 

can be corrected in the cont-

roller menu. This may be necessary if the values at the sensor do not correspond to
the room average (for example, if the sensor is positioned in a location which is war-
mer than average). Please be aware that usable measured values can only be achie-
ved approx. two hours after putting the sensor into operation (warm-up phase). 

Radio connections > Status

 (In the controller manual)

System > Installation > Radio connection > Status > [Device]

2.

Installation and commissioning

Installation, testing, operational start-up and troubleshooting should 
only be performed by an authorised electrician.

CAUTION!
Live voltage! 

There are unprotected live components inside the device.

• Inspect the device for damage before installation. Only put undamaged 
devices into operation. 
• Comply with the locally applicable directives, regulations and provisions for 
electrical installation. 
• Immediately take the device or system out of service and secure it against 
unintentional switch-on if risk-free operation is no longer guaranteed.

Use the device exclusively for building automation and observe the operating inst-
ructions. Improper use, modifications to the device or failure to observe the opera-
ting instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.1. Installation position

The 

Indoor Sensor WG AQS/TH gl

 is installed on a device socket.

May be installed and operated in dry interior rooms only. 
Avoid condensation.

When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interfe-
rence include:

Direct sunlight

Drafts from windows and doors

Draft from ducts which lead from other rooms or from the outside to the 
junction box in which the sensor is mounted

Waste heat from the control unit (when mounted above the display)

Warming or cooling of the building structure on which the sensor is mounted, 
e.g. due to sunlight, heating or cold water pipes

Connection lines and ducts which lead from warmer or colder areas to the 
sensor

Temperature deviations caused by such sources of interference must be corrected
in the control system menu, in order to achieve the specified sensor accuracy (see
manual chapter 

Wireless connections > Status

).

For a correct CO

2

 measurement it is necessary to install the device in a windproof

junction box.

2.2. Composition

2.2.1. Housing

Housing

Real glass, plastic

Colours

White, glossy (similar to RAL 9010 pure 
white) 

Mounting

on device socket according to DIN 49073

Protection category

IP 20

Dimensions

Housing approx. 55 x 55 (W x H, mm), 
mounting depth approx. 8 mm, 
base plate approx. 71 x 71 (W x H, mm)

Total weight 

approx. 50 g

Ambient temperature

Operating -20…+70°C, Storage -55…+90°C

Ambient air humidity

max. 95% RH, avoid bedewing

Operating voltage

11…28 V DC

Current

max. 120 mA

Data output

Wireless

Wireless frequency

868.2 MHz

Protocol

Proprietary protocol (Elsner RF)

Temperature measure-
ment range

-20…+70°C

Temperature resolution

0.1°C

Humidity measurement 
range

0% RH …95% RH

Humidity resolution

0.1%

Humidity drift

± 0.5% R.H. per year in normal air

CO

2

 measurement 

range 

0...2000 ppm

CO

2

 resolution 

1 ppm

Fig. 1: Sectional drawing.
The 

Indoor Sensor WG AQS/TH gl

 fits into a 

standard socket (Ø 60 mm, depth 42 mm).

Installation depth

27 mm

Mounting depth

8 mm

1

2

Fig. 2
1 Base plate
2 Openings for air circulation
3 Connection for power supply 11…28 V DC (polarity independent)
4 Catches
5 Programming LED (recessed)
6 Programming button (recessed) for teaching device

4

3

5

6