background image

Weather Station Suntracer KNX sl

1

Weather Station Suntracer KNX sl

 • Version: 08.10.2019 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

Suntracer KNX sl

Weather Station

Technical specifications and installation instructions

Item number 70154

1.

Description

The 

Weather Station Suntracer KNX sl

 for the KNX building bus system mea-

sures temperature, wind speed, brightness and air pressure. It recognises precipi-
tation and receives the GPS signal for time and location. In addition, using location
coordinates and the time, it calculates the exact position of the sun (azimuth and
elevation).

All values can be used for the control of limit dependent switching outputs. States
can be linked via AND logic gates and OR logic gates. Multi-function modules
change input data as required by means of calculations, querying a condition, or
converting the data point type. 
The integrated shade control system allows intelligent sun protection control of up
to 8 façades. 

The compact housing of the 

Suntracer KNX sl

 accommodates the sensors, eva-

luation circuits and bus-coupling electronics.

Functions:

Brightness measurement

 (current light strength) 

GPS receiver

, outputting the current time and location coordinates. The 

Weather Station Suntracer KNX sl

 also computes the position of the sun 

(azimuth and elevation)

Shade control

 for up to 8 façades with slat tracking and shadow edge 

tracking

Wind measurement

: The wind strength is measured electronically and 

thus noiselessly and reliably, even during hail, snow and sub-zero 
temperatures. Even turbulent air and rising winds in the vicinity of the  
device are recorded

Precipitation detection

: The sensor surface is heated, so that only drops 

and flakes are recognised as precipitation, but not mist or dew. When the 
rain or snow stops, the sensor is soon dry again and the precipitation 
warning ends

• Temperature measurement

Frost protection for shading systems

• Air pressure measurement

Weekly and calendar time switch

: All time switching outputs can be 

used as communication objects.
The 

weekly time switch

 has 24 periods. Each period can be configured 

either as an output or as an input. If the period is an output, then the 
switching time is set per parameter or per communication object.
The 

calendar time switch

 has 4 periods. Two on/off switching operations, 

which are executed daily, can be set for each period

Switching outputs

 for all measured and computed values. Threshold 

values can be adjusted per parameter or via communication objects

8 AND and 8 OR logic gates

, each with 4 inputs. All switching events as 

well as 16 logic inputs (in the form of communications objects) can be used 
as inputs for the logic gates. The output of each gate can be configured 
optionally as 1-bit or 2 x 8-bit

8 multi-function modules

 (computers) for changing the input data by 

calculations, by querying a condition or by converting the data point type

Summer compensation

 for cooling systems. A characteristic curve 

matches the target temperature in the room to the external temperature and 
sets the minimum and maximum target temperature values.

Configuration is made using the KNX software ETS. The 

product file

 can be dow-

nloaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the

“Service” menu.

1.0.1. Deliverables

Sensor

Connection cable approx. 10 m, with plug and connecting terminals

Surface-mounted junction box (IP 55, not weatherproof)

Worm-thread clamp Ø 40-60 mm

4×50 mm stainless steel roundhead screws and 6×30 mm dowels for wall 
mounting. Use fixing materials that are suitable for the base!

Fix mounting with installation accessories

1.1. Technical specification

Weather Station:

Mounting arm Fix:

The product conforms with the provisions of EU directives.

2.

Installation and start-up

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

CAUTION!
Live voltage! 

There are unprotected live components inside the device.

National legal regulations are to be followed.

Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.

Do not use the device if it is damaged. 

Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.

The device is only to be used for its intended purpose. Any improper modification
or failure to follow the operating instructions voids any and all warranty and gua-
rantee claims.

After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.

The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.

Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.2. Installation location

Select an installation position on the building where the sensors can measure
wind, rain and sunshine without hindrance. No structural elements should be
mounted above the weather station, from which water could continue to drop on
the precipitation sensor even after it has stopped raining or snowing. The weather
station should not be shaded by structures or, for example, trees. 

At least 60 cm of clearance must be left around the device. This facilitates correct
wind speed measurement without eddies. At the same time, this prevents spray
(raindrops hitting the device) or snow (snow penetration) from impairing the mea-
surement. The wind sensor must not come into contact with water. The distance
also prevents birds from biting the sensor.

The mounting position must be selected so that the sensors for rain and wind can-
not be touched by persons.

Please ensure that the extended awning does not cast shade on the device, and
does not protect the device against wind.

Temperature measurements can also be distorted by external influences such as
warming or cooling of the building structure on which the sensor is mounted (sun-
light, heating or cold water pipes). Temperature variations from such sources of in-
terference must be corrected in the ETS in order to ensure the specified accuracy
of the sensor (temperature offset).

Magnetic fields, transmitters and interference fields from electrical consumers
(e.g. fluorescent lamps, neon signs, switch mode power supplies etc.) can block or
interfere with the reception of the GPS signal.

2.2.1. Position of the sensors

ATTENTION!

Sensitive wind sensor.

Remove the protective transport sticker after installation.

Do not touch the sensor on the wind measuring element 
(on bottom, recessed).

Housing

Plastic

Colour

White / Translucent

Assembly

Surface mount

Protection category

IP 44

Dimensions

approx. 62 × 71 × 152 (W × H × D, mm)

Connection cable

4-wire (bus +/-, auxiliary v/-), 
diameter approx. 5 mm

Weight

weather station with mounting approx. 90 g,
total weight with accessories approx. 280 g

Ambient temperature

Operation -30…+50°C, storage -30…+70°C

Auxiliary supply

12…40 V DC, 12…28 V AC. An appropriate 
power supply unit can be purchased from 
Elsner Elektronik.

Auxiliary current

at 12V DC: max. 185 mA
at 24V DC: max. 90 mA
at 24V AC: max. 82 mA

Bus current

max. 10 mA

Data output

KNX +/-

BCU type

Integrated microcontroller

PEI type

0

Group addresses

max. 2000

Assignments

max. 2000

Communication 
objects

1387

Temperature sensor:
Measurement range 

-30°C … +50°C

Resolution

0.1°C

Accuracy

±0.5°C at -30°C … +25°C
±1.5°C at -30°C … +45°C

Wind sensor:
Measurement range

0 m/s … 35 m/s

Resolution

0.1 m/s

Accuracy

±15% of the measurement value when inco-
ming flow is 45°…315°
(Frontal incoming flow corresponds to 180°)

Pressure sensor:
Measurement range

300 mbar … 1100 mbar

Resolution

0.1 mbar

Accuracy

±4 mbar

Brightness sensor:
Measurement range

0 lux … 150,000 lux

Resolution

  1 lux up to 300 lux
  2 lux up to 1000 lux 
25 lux up to 150.000 lux

Accuracy

±15% of the measurement value at 30 lux … 
30,000 lux

Colour

powder-coated white RAL 9003

Total lenght

approx. 430 mm

Weight

approx. 190 g

Fig. 1
There must be at least 60 cm clearance 
to other elements (structures, cons-
truction parts, etc.) below, to the sides 
and in front of the device.

60 cm

Fig. 2
The device must be attached to a ver-
tical wall (or a pole).

Place the supply line in a loop before 
leading it into the wall or junction box. 
This will allow rain to drip off and not 
drain into the wall or box.

Wall
or
pole

90°

Fig. 3
The device must be mounted in the 
horizontal (transverse) direction.

Horizontal

Fig. 4
For installation in the northern hemis-
phere, the device must be aligned to 
face south. 

For installation in the southern hemis-
phere, the device must be aligned to 
face north.

North

South

1 Brightness sensor
2 Precipitation sensor (area with 

tracks)

3 Position of temperature sensor
4 Wind measuring element

3

2

1

4

Fig. 5

EN

Отзывы: