background image

Weather Station Suntracer KNX basic

1

Weather Station Suntracer KNX basic

 • Version: 01.06.2021 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

Suntracer KNX basic

Weather Station

Technical specifications and installation instructions

1.

Description

The 

Weather Station Suntracer KNX basic

 perceives temperature, wind

speed, brightness and precipitation. All data may be used for the control of swit-
ching outputs which depend on threshold values. The states may be linked by me-
ans of AND and OR logic gates. The compact housing of 

Suntracer KNX basic

stores the sensor system, the evaluation electronics and the electronics of the bus
connection.

Functions:

Brightness measurement

: The current light intensity is measured by 

means of a sensor

Wind measurement

: The measurement of wind speed is accomplished 

electronically and thus noiseless and reliable even in case of hail, snow and 
minus temperature. Air swirls and up-draught in the radius of the weather 
station are collected, too

Wind sensor monitoring

: If the wind measurement value changes by less 

than ± 0.5 m/s within 48 hours, a fault can be output. The wind measured 
value is output with the maximum measured value of 35 m/s and all wind 
threshold values below this value become active

Precipitation perception

: The surface of the sensor is heated so that only 

drops and flakes are recognised as precipitation but not fog or dew. If it 
stops raining or snowing, the sensor dries quickly and the precipitation 
message ends

Temperature measurement

 

Threshold values

 can be adjusted per parameter or via communication 

objects

8 AND and 8 OR logic gates

 with each 4 inputs. Every switching incident 

as well as 8 logic inputs (in the form of communication objects) may be used 
as inputs for the logic gates. The output of each gate may optionally be 
configured as 1 bit or 2 x 8 bits

Configuration is made using the KNX software ETS. The 

product file

 can be dow-

nloaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the

“Service” menu.

1.1. Scope of delivery

Weather station with combined wall/pole mounting

2x stainless steel installation band for pole installation

1.2. Technical specifications

The product conforms with the provisions of EU directives.

2.

Installation and commissioning

Installation, testing, operational start-up and troubleshooting should 
only be performed by an authorised electrician.

DANGER!
Risk to life from live voltage (mains voltage)! 

There are unprotected live components inside the device.

• Inspect the device for damage before installation. Only put undamaged 
devices into operation. 
• Comply with the locally applicable directives, regulations and provisions 
for electrical installation. 
• Immediately take the device or system out of service and secure it against 
unintentional switch-on if risk-free operation is no longer guaranteed.

Use the device exclusively for building automation and observe the operating ins-
tructions. Improper use, modifications to the device or failure to observe the ope-
rating instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in
the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.0.1. Location

Select an assembly location at the building where wind, rain and sun may be col-
lected by the sensors unobstructedly. Do not assemble any construction compo-
nents above the weather station from where water may drop on to the rain sensor
after it has stopped raining or snowing. The weather station may not be shaded by
the building or for example by trees. 

At least 60 cm of clearance must be left all round the weather station. This facilita-
tes correct wind speed measurement without eddies. The distance concurrently
prevents spray (raindrops hitting the device) or snow (snow penetration) from im-
pairing the measurement. It also does not allow birds to bite it. Please ensure that
the extended awning does not cast shade on the unit, and that this is not protected
from the wind.

Temperature measurements can also be affected by external influences such as by
warming or cooling of the building structure on which the sensor is mounted, (sun-
light, heating or cold water pipes). Temperature variations from such sources of in-
terference must be corrected in the ETS in order to ensure the specified accuracy
of the sensor (temperature offset).

2.1. Mounting the weather station

2.1.1. Attaching the mount

The sensor comes with a combination wall/pole mount. The mount comes adhered
by adhesive strips to the rear side of the housing. Fasten the mount vertically onto
the wall or pole. 

2.1.2. View of rear side and drill hole plan 

Housing

Plastic material

Colour

White / translucent

Mounting

On-wall

Degree of protection

IP 44

Dimensions

approx. 96 × 77 × 118 (W × H × D, mm)

Weight 

230 V AC version: approx. 240 g
20...32 V DC version: approx. 170g

Ambient temperature

Operation -30…+50°C, Storage -30…+70°C

Operating voltage

Available for 230 V AC or for 20...32 V DC
An appropriate power supply unit can
be obtained from Elsner Elektronik.

Current

230 V AC version: max. 20 mA
20...32 V DC version: max. 100 mA
Residual ripple 10%

Data output

KNX +/- bus terminal plug

Group addresses

max. 254

Allocations

max. 255

Communication objects

109

Heating rain sensor

approx. 1.2 W

Measurement range 
temperature

-40…+80°C

Resolution (tempera-
ture)

0.1°C

Accuracy (temperature)

±1°C    at -10…+85°C
±1.5°C at -25…+150°C

Item number 
3095 (230 V AC), 
3096 (20...32 V DC)

Measurement range 
wind

0…35 m/s

Resolution (wind)

0,1 m/s

Accuracy (wind)

at ambient temperature -20…+50°C:
±22% of the measurement value when inci-
dent flow is from 45…315°
±15% of the measurement value when inci-
dent flow is from 90…270°
(Frontal incident flow corresponds to 180°)

Measurement range 
brightness

0 ... 150,000 lux

Resolution (brightness)

    1 lux up to 300 lux
    2 lux up to 1,000 lux
  25 lux up to 150,000 lux

Accuracy (brightness)

±15% of the measurement value at 30 lux … 
120,000 lux

Fig. 1
There must be at least 60 cm of space 
below, to the sides and in front of the 
weather station left from other ele-
ments (structures, construction parts, 
etc.).

60 cm

Fig. 2
The wind sensor must be mounted 
onto a vertical wall (or pole).

Wall
or 
pole

Fig. 3
The wind sensor must be mounted ho-
rizontally in the lateral direction.

Horizontal

Fig. 4
The weather station must be aligned 
in the 
direction of the façade on which shade 
is to be provided.

Facade

Fig. 5

When wall mounting: flat side on wall, 
crescent-shaped collar upward.

Collar

Fig. 6

When pole mounting: curved side on po-
le, collar downward.

Collar

Fig. 7
Different mounting arms are available 
from Elsner Elektronik as additional, op-
tional accessories for flexible installation 
of the weather station on a wall, pole or 
beam (pictures of sensors exemplary).
Example of the use of a mounting arm: 
Due to  flexible ball joints, the sensor can 
be brought into ideal position.

Fig. 8
Example use of the hinge arm mounting:
With the hinge arm mounting, the weat-
her station projects from beneath the 
roof overhang. Sun, wind and precipita-
tion can act upon the sensors without 
hindrance.

Fig. 9
Example use of the hinge arm mounting:
Fitting to a pole with worm drive hose 
clips

Langloch 7,5 x 5 mm

Fig. 10 a+b

Drill hole plan

Dimensions of rear side of housing with bra-
cket. Subject to change for technical enhan-
cement.

EN

Отзывы: