38
Parameter setting
Sensors Mini-Sewi KNX TH-L-Pr and Mini-Sewi KNX L-Pr
• Version: 30.08.2018 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when
blocked.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
6.9.
Temperature PI control
The chapter "Temperature PI control" only applies to the TH-L-Pr
model.
Activate the control if you want to use it.
General control
Set, in which cases
setpoint values and extension time
received via object are to
be retained. The parameter is only taken into consideration if the setting via object is
activated below. Please note that the setting "After power supply restoration and pro-
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before
1st communication
0 • 1
Behaviour of the switching output
On block
• Do not send message
• send 0
• send 1
On release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
• Do not send message
• Send switching output status
Switching output sends on change to 1
• Do not send message
• if switching output = 1
send 1
Switching output sends on change to 0
• Do not send message
• if switching output = 0
send 0
Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1
and periodically
if switching output = 1
send 1
Switching output sends on change to 0
and periodically
if switching output = 0
send 0
Use control
No • Yes