background image

Sensor KNX TH-UP Touch

1

Sensor KNX TH-UP Touch

 • Version: 19.07.2017 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de • 

Technical Service: +49 (0) 7033 / 30945-250

EN

KNX TH-UP Touch

Combined Indoor Sensor

Technical specifications and installation instructions

Item numbers 70615 (white), 70616(black)

1.

Description

The 

Sensor KNX TH-UP Touch

 measures temperature and humidity and calcula-

tes the dew point. The sensor can receive external measured values via the bus and
process them with the own data to overall values (mixed values, e. g. room avera-
ge). The 

KNX TH-UP Touch

 offers two push buttons that may be used for changing

the ambient temperature (target value), for switching between operating modes or
as free programmable bus push buttons.

The 

KNX TH-UP Touch

 provides switching outputs with adjustable threshold valu-

es. The switching outputs and further communication objects can be linked by AND
and OR logic gates. Additionally, an integrated actuating variable comparator can
compare and output values that are received via communication objects.

Integrated PI controllers allows for control of a ventilation (depending on air humi-
dity) and a heating/cooling system (depending on temperature). The 

KNX TH-UP

Touch

 can emit a warning to the bus as soon as the area of optimum comfort (ac-

cording to DIN 1946) is left.

The integrated display shows the own values and data received from the bus (e.g.
date, time). The device is completed with a frame of the switching series installed in
the building and thus merges with the interior.

Functions:

Measurement of 

temperature

 and 

air humidity

 (absolute and relative), 

calculation of the dew point 

Mixed values

 from own measured values and external values (proportions 

can be set in percentage) 

Display

 1-3 rows (own values or values received from the bus) or display of 

temperature control (see 

Mode display and manual temperature controller

page 2)

2 push buttons

. Configuration as bus push button or for changing ambient 

temperature and switching between operating modes (see 

Change ambient 

temperature with the buttons

, page 2)

PI controller for heating

 (one or two step) and 

cooling

 (one or two step) 

depending on temperature. Control according to separate target values or 
basic target temperature

PI controller for ventilation

 depending on humidity: dehumidification/

humidification (one step) or dehumidification (one or two step)

Threshold values 

can be adjusted per parameter or via communication 

objects: 3 × temperature, 2 × humidity

4 AND and 4 OR logic gates

 with each 4 inputs. Every switching incident 

as well as 16 logic inputs in the form of communication objects, may be used 
as inputs for the logic gates. The output of each gate may optionally be 
configured as 1 bit or 2 x 8 bits

2 actuating variable comparators

 for output of minimum, maximum or 

average values. Each with 5 inputs (for values received via communication 
objects)

Configuration is made using the KNX software ETS 5. The 

product file

 can be

downloaded from the ETS online catalogue and the Elsner Elektronik website on

www.elsner-elektronik.de

 in the “Service” menu.

1.0.1. Scope of delivery

Housing with display

Base plate

You will need

 in addition

 (not supplied):

Socket Ø 60 mm, 42 mm deep 

Frame (for element 55 x 55 mm), suitable for the switching programme used 
in the building

1.1. Technical specifications

The product conforms with the provisions of EU guidelines.

1.1.1. Accuracy of the measurement

Measurement variations from permanent sources of interference (see chapter 

Ins-

tallation position

) can be corrected in the ETS in order to ensure the specified ac-

curacy of the sensor (offset).

When 

measuring temperature

, the self-heating of the device is considered by the

electronics. The heating is compensated by the software.

2.

Installation and commissioning

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

CAUTION!

Live voltage! 

There are unprotected live components inside the device.

National legal regulations are to be followed.

Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.

Do not use the device if it is damaged. 

Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.

The device is only to be used for its intended purpose. Any improper modification
or failure to follow the operating instructions voids any and all warranty and gua-
rantee claims.

After unpacking the device, check it immediately for possible mechanical damage.
If it has been damaged in transport, inform the supplier immediately.

The device may only be used as a fixed-site installation; that means only when as-
sembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.

Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.

2.2. Installation position

The 

Sensor KNX TH-UP Touch

 is made for wall mounting in a socket (Ø 60 mm,

42 mm deep).

May be installed and operated in dry interior rooms only. 
Avoid condensation.

Housing

ABS plastic material

Colours

• White
• Black

Mounting

In-wall (wall mounting in socket 

Ø

60 mm, 

42 mm deep, resp. cavity wall socket for hole 

Ø

 68 mm)

Protection category

IP 20

Dimensions

Housing approx. 55 x 55 (W x H, mm), 
mounting depth approx. 8 mm, 
base plate approx. 71 x 71 (W x H, mm)

Total weight 

approx. 50 g

Ambient temperature

Operation 0…+50°C, storage -10…+60°C

Ambient air humidity

max. 95% RH, avoid bedewing

Operating voltage

KNX bus voltage

Bus current

max. 10 mA

Data output

KNX +/- bus terminal plug

BCU type

Own micro controller

PEI type

0

Group addresses

max. 254

Allocations

max. 254

Communication 
objects

186

Temperature measure-
ment range

0…+50°C

Temperature resolution

0.1°C

Temperature accuracy

± 0,5°C at 0…+50°C
(Mind the notes on 

Accuracy of the measure-

ment

, page 1)

Humidity measurement 
range

0% RH …95% RH

Humidity resolution

0.1%

Humidity accuracy

±7,5% RH at   0...10% RH
±4,5% RH at 10...90% RH
±7,5% RH at 90...95% RH

Humidity drift

± 0.5% R.H. per year in normal air

Fig. 1: Sectional drawing.
The 

Sensor KNX TH-UP Touch

 fits into a nor-

mal socket (Ø 60 mm, depth 42 mm).

The frame is not included!

Отзывы: