Transmission protokoll
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
3. Transmission protokoll
3.1. List of all Communication objects
Abbreviations Flags:
C
Communication
R
Read
W Write
T
Transmit
U
Update
No
Name
Function
DPT
Flags
0
Software version
readable
217.001
C R T
1
Malfunction temperature/humidity
sensor
Output
1.001
C R T
2
CO2 sensor malfunction
Output
1.001
C R T
3
External measured value for tem-
perature
Input
9.001
C W
4
Internal measured value for tem-
perature
Output
9.001
C R T
5
Total measured value for temperature
Output
9.001
C R T
6
Request min./max. temperature mea-
sured value
Input
1.017
C W
7
Minimum measured value for tem-
perature
Output
9.001
C R T
8
Maximum measured value for tem-
perature
Output
9.001
C R T
9
Reset min./max. measured value for
temperature
Input
1.017
C W
10
Temp. threshold value 1: Absolute
value
Input / output
9.001
C R W T U
11
Temp. threshold value 1: (1:+ | 0:-)
Input
1.002
C W
12
Temp. threshold value 1: Switching
delay from 0 to 1
Input
7.005
C W
13
Temp. threshold value 1: Switching
delay from 1 to 0
Input
7.005
C W
14
Temp. threshold value 1: Switching
output
Output
1.001
C R T
15
Temp. threshold value 1: Switching
output block
Input
1.002
C W
16
Temp. threshold value 2: Absolute
value
Input / output
9.001
C R W T U