Cala KNX T 101
Room Temperature Controller
Technical specifications and installation instructions
Item numbers 70980 (white), 70982 (black)
1.
Description
The
Room Temperature Controller Cala KNX T 101
measures the room tem-
perature and displays the current value in white illuminated figures. Via the bus the
device can receive an external measured value and process it with own data to ove-
rall temperature value (mixed value).
The
Cala KNX T 101
has got an integrated PI controller for a heating and a cooling
system (one or two step). The room temperature is adjusted by means of the „+“
and „-“ touch buttons.
The device is supplemented with a frame of the switch series used in the building,
and thus fits seamlessly into the interior fittings.
Functions:
•
Measurement of
temperature
.
Mixed value
from own measured value and
external values (proportions can be set in percentage), output of minimum
and maximum values
•
Display
of the actual value or the target value/basic setpoint shift
•
2 touch buttons
(+/-) for adjustment of the room temperature
•
PI controller for heating
(one or two step) and
cooling
(one or two step)
depending on temperature. Control according to separate target values or
basic target temperature
Configuration is made using the KNX software as of ETS 5. The
product file
can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de
in the “Service” menu.
1.0.1. Scope of delivery
•
Room temperature controller in casing
•
Base plate
Additionally
required (not included in the deliverables):
•
Windproof device socket according to DIN EN IEC 60670-1 and DIN 49073
•
Frame (for insert 55 x 55 mm), compatible to the switch scheme used in the
building
1.1. Technical data
The product is compliant with the provisions of EU Directives.
1.1.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter
Ins-
tallation position
) can be corrected in the ETS in order to ensure the specified accu-
racy of the sensor (offset).
When
measuring temperature
, the self-heating of the device is compensated.
2.
Installation and commissioning
Installation, testing, operational start-up and troubleshooting should
only be performed by an authorised electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• Inspect the device for damage before installation. Only put undamaged
devices into operation.
• Comply with the locally applicable directives, regulations and provisions for
electrical installation.
• Immediately take the device or system out of service and secure it against
unintentional switch-on if risk-free operation is no longer guaranteed.
Use the device exclusively for building automation and observe the operating inst-
ructions. Improper use, modifications to the device or failure to observe the opera-
ting instructions will invalidate any warranty or guarantee claims.
Operate the device only as a fixed-site installation, i.e. only in assembled condition
and after conclusion of all installation and operational start-up tasks, and only in the
surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may
occur after publication of these operating instructions.
2.1. Installation position
The
Room Temperature Controller Cala KNX T 101
is installed on a device so-
cket.
May be installed and operated in dry interior rooms only.
When selecting an installation location, ensure that the measurement results are af-
fected as little as possible by external influences. Possible sources of interference
include:
•
Direct sunlight
•
Drafts from windows and doors
•
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
•
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected
in the ETS in order to ensure the specified accuracy of the sensor (offset).
2.2. Device structure
2.2.1. Casing
2.3. Installation of the sensor
First install the windproof socket with feed line. Seal the inlet tubes as well, in order
to prevent draughts.
Casing
Genuine glass, plastic
Colours
• similar to RAL 9010 pure white
• similar to RAL 9005 deep black
Installation
on device socket according to
DIN EN IEC 60670-1 and DIN 49073
Degree of protection
IP 20
Dimensions
Housing approx. 55 x 55 (W x H, mm),
Installation depth approx. 10 mm,
Base plate approx. 71 x 71 (W x H, mm)
Total weight
approx. 50 g
Ambient temperature
Operating -5…+45°C, storage -30…+85°C
Ambient humidity
5...95% RH, avoid condensation
Operating voltage
KNX bus voltage
Bus current
max. 15 mA
Data output
KNX +/- Bus plug-in terminal
Group addresses
max. 183
Allocations
max. 183
Communication
objects
41
Temperature measu-
rement range
-5…+60°C
Fig. 1: Sectional drawing.
The
Room Temperature Controller
Cala KNX T 101
fits in a standard con-
nector socket (Ø 60 mm, depth 42 mm).
The frame is not included in the delive-
ry!
Installation depth
27 mm
Construction depth
10 mm
Fig. 2: Front
1 Ventilation slit (top and bottom)
2 Temperatur display
3 Touch area -
4 Touch area +
2
1
4
1
3
Fig. 3: Back
1 Base frame
2 KNX terminal BUS +/-
3 Programming button (reces-
sed) for teaching the device
4 Programming LED (recessed)
5 Catches
5
1
3
2
4