Setting the parameters
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
Setpoint values for frost/heat protection (building protection)
The building protection mode is for example used as long as windows are opened for
ventilation. Setpoints for frost protection (heating) and heat protection (cooling) are
determined which may not be modified from outside (no access via operating devices
etc.). The building protection mode may be activated with delay, which allows you to
leave the building before the controls switch to frost/heat protection mode.
General control variables
This setting appears for the control types "Heating
and
Cooling" only. Here, you can
decide whether to use a common control variable for heating and cooling. If the 2nd
level has a common control variable, you also determine the control mode of the 2nd
level here.
When using the control variable for a 4/6 way valve, the following applies:
0%...100% heating = 66%...100% control variable
OFF = 50% control variable
0%...100% cooling = 33%...0% control variable
9.4.1. Heating control level 1/2
If a heating control mode is configured, one or two setting sections for the heating lev-
els are displayed.
In the 1st level, heating is controlled by a PI control, which allows to either enter control
parameters or select predetermined applications.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI
or a 2-point-control.
Setpoint frost protection (in 0.1°C)
-300…800; 70
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
Setpoint heat protection (in 0.1°C)
-300…800; 350
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
For heating and cooling
• separate control variables are used
• common control variables are used for
Level 1
• common control variables are used for
Level 2
• common control variable are used for
Level 1+2
Use control variable for 4/6-way valve
(only for common control variables
in level 1)
No • Yes
Control type
(for level 2 only)
• 2-point-control
• PI control
Control variable of the 2nd Level is on
(only for level 2 with 2 point controlling)
• 1 bit object
• 8 bit object