14
Setting parameters
Actuator KNX R1-B4 compact 16 A
• Version: 28.05.2020 • Technical changes and errors excepted.
Switch on delay
The switch on delay is set with time base and time factor (e.g. 1 min × 4 corresponds
to 4 minutes). In addition, it is determined whether the time span is extended when a
switch on telegram is received again ("can be retriggered", e.g. by pressing the switch
again) and what happens if a switch off telegram arrives from the bus.
Switch off delay
The switch off delay is set with time base and time factor (e.g. 1 min × 4 corresponds
to 4 minutes). In addition, it is determined whether the time span is extended when a
switch off telegram is received again ("can be retriggered", e.g. by pressing the switch
again) and what happens if a switch on telegram arrives from the bus.
6.3.4. Staircase time switch
The menu item only appears if the staircase light function is selected in the settings for
the switch function channel. The staircase light time function ensures, for example,
that light is on for a while and then switches itself off.
With staircase light timer switching, the time base and time factor are used to set how
long the light remains on (e.g. 1 s × 10 corresponds to 10 seconds). In addition, it is de-
termined whether the time span is extended when a switch on telegram is received
again ("can be retriggered", e.g. by pressing the switch again) and what happens if a
switch off telegram arrives from the bus.
Switch on delay:
Time basis
0,1 s … 1 h; 1 min
Time factor
4 … 255; 10
Switch on delay is
cannot be retriggered• can be retriggered
Off telegram during switch on delay causes
• nothing
• cancellation of the switch on delay
Switch off delay:
Time basis
0,1 s … 1 h; 1 min
Time factor
4 … 255; 10
Switch off delay is
Cannot be retriggered• can be retriggered
On telegram during switch on delay causes
• nothing
• cancellation of the switch off delay
Time basis
0,1 s • 1 s • 1 min • 1 h
Time factor
4...255; 10
Staircase light time
cannot be retriggered• can be retriggered
Off telegram during staircase light time
causes
nothing • direct switch off