Setting parameters

Actuator KNX R1-B4 compact 16 A

 • Version: 28.05.2020 • Technical changes and errors excepted.

6.1.

Behaviour on power failure/ restoration of 
power

Behaviour following a failure of the bus power supply:

The device sends nothing.

Behaviour on bus restoration of power and following programming or reset:

The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.

6.2.

General settings

First set the general parameters for the bus communication (message rate, transmis-
sion delays). In addition, you can specify whether all or only the changed settings are
transferred to the bus when programming scenes.

The 

label for objects

 is placed in front of all the objects of 

Actuator KNX R1-B4

compact 16 A

, making their assignment more recognisable in the ETS.

Activate the switch function

Input 1

  can be used as actuator button or bus button. The 

inputs 2-4 

are bus buttons.

6.3.

Switch function

The 

label for channel objects

 is placed in front of all the objects of this channel, mak-

ing their assignment more recognisable in the ETS.

The 

Scenes

 menu is activated here.

Transmission delay of switching and status
outputs after power restoration

5 s … 2 h

When using scenes:

Transfer when programming

All parameters • only changed parameters

Object labelling

[Free text max. 20 characters]

Channel A

Do not use • 

switch function

Operating mode

Use input 1

• No 
• as a bus button 
• as an actuator button 

Use input 2 (3 / 4)

No • Yes

Label for channel objects

[Free text max. 20 characters]

Use scenes
(see the Scenes chapter)

No • Yes

Содержание 70574

Страница 1: ...EN Installation and Adjustment KNX R1 B4 compact 16 A Switching Actuator Item number 70574 ...

Страница 2: ......

Страница 3: ... output 7 2 4 Instructions for assembly and operational start up 8 3 Addressing of the device at the bus 8 4 Disposal 8 5 Transfer protocol 9 5 1 List of all communication objects 9 6 Setting parameters 10 6 1 Behaviour on power failure restoration of power 11 6 2 General settings 11 6 3 Switch function 11 6 3 1 Relationship between logic operation timer switch Block 12 6 3 2 Linking 13 6 3 3 Swit...

Страница 4: ...leshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided WARNING indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided CAUTION i...

Страница 5: ...case lighting timer switch with adjustable pre warning light blinks prior to switch off Scene control for switching state with 8 scenes 4 binary inputs Configuration is made using the KNX software ETS 5 The product file can be down loaded from the ETS online catalogue and the Elsner Elektronik website on www els ner elektronik de in the Service menu 1 0 1 Scope of delivery Actuator Connection line...

Страница 6: ...n is no longer guaranteed The device is only to be used for the intended purpose described in this manual Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical damage If it has been damaged in transport inform the supplier immediately The device may only be us...

Страница 7: ...ts driven by an electric motor Adhere to the relevant building regulations Ensure that the return path access to the building is not blocked if spending time outside the building danger of being locked out Correctly decommission the system for maintenance and cleaning work If there is a power outage the system does not work Therefore shadings should be moved to a save position if there are anticip...

Страница 8: ...s while installing and cable laying of the KNX connection and inputs The physical address is assigned by the KNX software There is a button with a control LED for this on the actuator To connect the digital inputs fig 1 no 1 use the attached breakout cable The cables for the inputs can be extendet to up to 10 m All GND connections of the inputs are bridged internally black cable Fig 1 1 Digital in...

Страница 9: ... 1 Connection examples output Fig 2 Breakout cable for digital inputs Input 1 black GND white Input 2 black GND yellow Input 3 black GND violet Input 4 black GND blue KNX R1 B4 compact 16A Nr 70574 PRG UA1 OUT A1 LED PE N L L N PE Mains 230 V AC One consumer load Each terminal contact may be loaded with a maximum of 16 A ...

Страница 10: ...ng this phase no information can be received or sent via the bus 3 Addressing of the device at the bus The device is supplied with the bus address 15 15 255 You can program another ad dress into the ETS by overwriting the 15 15 255 address or by teaching via the pro gramming button 4 Disposal After use the device must be disposed of or recycled in accordance with the legal reg ulations Do not disp...

Страница 11: ...t WC 1 10 DPT_Start 1 Bit 7 Channel A1 Linking Input WC 1 2 DPT_Bool 1 Bit 8 Channel A1 Call up saving scenes Input RWC 18 1 DPT_SceneControl 1 Byte 9 Input 1 Extended Input Output RWCT 1 8 DPT_UpDown 1 Bit 10 Input 1 Short Output R CT 1 8 DPT_UpDown 1 Bit 11 Input 1 Switching Input Output RWCT 1 1 DPT_Switch 1 Bit 12 Input 1 Relative dimming Input Output RWCT 3 7 DPT_Control_ Dimming 4 Bit 13 Inp...

Страница 12: ...ming Input Output RWCT 3 7 DPT_Control_ Dimming 4 Bit 31 Input 3 Encoder 8 Bit Output R CT 5 5 xxx 1 Byte 32 Input 3 Temperature encoder Output R CT 9 1 DPT_Value_Temp 2 Bytes 33 Input 3 Brightness encoder Output R CT 9 4 DPT_Value_Lux 2 Bytes 34 Input 3 Scene Output R CT 18 1 DPT_SceneControl 1 Byte 35 Input 3 Blocking object Input WC 1 1 DPT_Switch 1 Bit 36 Input 4 Extended Input Output RWCT 1 8...

Страница 13: ...g scenes The label for objects is placed in front of all the objects of Actuator KNX R1 B4 compact 16 A making their assignment more recognisable in the ETS Activate the switch function Input 1 can be used as actuator button or bus button The inputs 2 4 are bus buttons 6 3 Switch function The label for channel objects is placed in front of all the objects of this channel mak ing their assignment m...

Страница 14: ...an be set up If required activate the Block function menu in which you can define a block 6 3 1 Relationship between logic operation timer switch Block Application example Staircase light that is only to be switched at twilight night link and that is switched on in the event of a fire alarm block Relay operation Closer Opener Behaviour following a bus voltage drop no change opened closed Behaviour...

Страница 15: ...nput active AND twilight ac tive 6 3 3 Switch on and off delay The menu item only appears if a switch on or switch off delay is selected in the settings for the switch function channel The menu item has the same name as the selected function With the switch on and switch off delay for example a switch for ventilation device and light can be used However due to the switch on delay the ventilator do...

Страница 16: ...unction channel The staircase light time function ensures for example that light is on for a while and then switches itself off With staircase light timer switching the time base and time factor are used to set how long the light remains on e g 1 s 10 corresponds to 10 seconds In addition it is de termined whether the time span is extended when a switch on telegram is received again can be retrigg...

Страница 17: ...t Channel call save scenes of the actuator is linked to this group ad dress A scene is called then the scene number is communicated to the actuator The state stored in the actuator for this scene number is switched If the scene saving function is used then the switch state is saved for this scene num ber in the actuator The Scenes menu item of the actuator only appears if Use scenes is selected in...

Страница 18: ...d in the program file of the actuator The inputs can be configured very easily as switches drive controls dimmers for sending values and for scene recall Input as switch If a button with switching function is assigned to the input select the bus function Switch and define which value is sent when the button is pressed released and when it is sent Switch state inactive active Bus function Switch Ch...

Страница 19: ...n shutter awn ing blind or window and define the button function and the control mode A detailed description of the setting options for the individual control modes can be found in chapter Control modes for drive control page 20 Cycle if sent periodically 5 s 10 s 30 s 1 min 2 min 5 min 10 min 20 min 30 min 1 h 2 h Use blocking object No Yes When activating the block once send 0 send 1 Do not send...

Страница 20: ...an be disabled with a blocking object For active blocking there is no bus communication Input as temperature encoder If the input is to be used as a temperature encoder select the bus function Tempera ture encoder and define which value is to be transmitted between 30 C and 80 C By sending a temperature value for example the set point of the temperature control can be changed Use blocking object N...

Страница 21: ...Scenes and specify the storage time difference call storage and scene number The input can be disabled with a blocking object For active blocking there is no bus communication 6 4 2 Input as actuator Input 1 can be defined as bus or actuator button The inputs 2 4 are bus buttons Input as switch If a button with switching function is assigned to the input select the bus function Switch and define w...

Страница 22: ...e block is active there is no bus communication and no operation is possible 6 4 3 Control modes for drive control If inputs are being used as switches to operate shades or windows then various con trol modes can be set Command when pressing the button Switch off Switch on nothing Command when releasing the button Switch off Switch on nothing Use blocking object No Yes When activating the block on...

Страница 23: ...olding it slightly longer longer than Time 1 but shorter than Time 1 2 Drive run ning Drive stops when the button is released Long holding release after Time 1 2 runs out Drive moves independently to the end position The movement can be interrupted by a short tap Control mode Standard Behavior during button operation short stop increment long Up or Down Time between short and long in 0 1 seconds 1...

Страница 24: ...ton is released Control mode Comfort mode Behavior during button operation Button is pushed and released before time 1 expired stop step held longer than time 1 Up or Down released between time 1 and 1 2 stop released after time 1 2 no more stop Time 1 0 0s 2 s 0 4 s Time 2 0 s 2 s 2 s Control mode Dead man s switch Behavior during button operation Push button Up or Down command Release button Sto...

Страница 25: ......

Страница 26: ...mbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49 0 70 33 30 945 250 ...

Отзывы: