Parameter setting
Actuator KNX S1R-BA4-UP 24 V
• Version: 27.05.2020 • Technical changes and errors excepted.
If monitoring periods or movement range limits are used, no operation via the local
button is possible in case of a bus voltage failure.
Input as zero position sensor
The zero position sensor is used for the movement range limit of the respective drive
(see
, page 21). In case of a defect zero position sensor a
malfunctioning message can be sent to the bus.
6.2.2. Output channel with drive
Control modi for drive control
If inputs are used as buttons for operating shading or windows, then different control
modi can be set.
Standard:
If briefly operated, the drive will move incrementally or stops. If operated longer, the
drive will move up to the end position. The time difference between "short" and "long"
is set individually.
Standard inverted:
When pushed shortly, the drive moves up to the end position. When pushed for longer,
the drive moves incrementally or stops. The time difference between "short" and
"long" and the repeat interval is set individually.
Send malfunction message when zero
position sensor is defective
No • Yes
Control mode
• Standard
• Standard inverted
• Comfort mode
• Dead man's switch
Control mode
Standard
Behavior during button operation:
short = stop/increment long = Up or Down
Time between short and long
in 0.1 seconds
1...50; 10
Control mode
Standard inverted
Behavior during button operation:
short = Up or Down long = Stop/Step
Time between short and long
in 0.1 seconds
1...50; 10
Repeat the step command
for a long button press
every 0.1 s • every 2 sec; every 0.5 sec