87
Installation
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
Installation of the control unit WS1 Color
Warning, mains voltage! National legal regulations are to be
observed. Installation, inspection, commissioning and
troubleshooting of the device must only be carried out by a
competent electrician.
Preparing the installation location
The device must only be installed and used in dry, interior
spaces. Avoid condensation.
The device is to be installed flush to the wall surface. When selecting an installation
location, please ensure that the measurement results of the integrated temperature/
humidity sensor are affected as little as possible by external influences. Possible sourc-
es of interference include:
•
Direct sunlight
•
Drafts from windows and doors
•
Draft from ducts which lead from other rooms to the concealed box
•
Warming or cooling of the building structure on which the device is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines which lead from warmer or colder areas to the device
An external antenna can be connected in order to improve wireless communications.
During installation, a
conduit 50 cm in length
should be placed beneath the re-
cessed housing, in which the external antenna can be mounted (antenna dimensions
approx. 565 x 8 x 5, L × W × H in mm):
External dimensions
of concealed box
in mm:
(depth approx. 62 mm)