64
Automatic settings
Control System WS1 Color / WS1000 Color
• Version: 14.12.2016 • Technical changes and errors excepted.
long this temperature has been exceeded. It is a maximum of one third of the set trig-
ger period (e.g. max. 12 hours for a 48-hour trigger period).
3.2.6. Adjust frost alarm
The frost alarm for shades and windows will be active when during or after precipita-
tion the outdoor temperature falls below a defined level.
The weather data display (Start screen) then shows “Frost alarm” next to the outdoor
temperature value. The display can also show “Night-time re-cooling” and “Window
movement limitation” in turn.
2.1. Weather data display (start screen)
You adjust which shades will be retracted and which windows will be closed in the au-
tomatic functions for the individual shades and windows.
The following situations trigger the frost alarm:
•
The outdoor temperature is below the set frost alarm temperature and ist starts
to rain/snow.
•
The outdoor temperature falls below the set frost alarm temperature while it is
raining/snowing.
•
Rain/snow has stopped. The outdoor temperature falls belowing the set frost
alarm temperature within the set standby period after the end of precipitation.
The following situation stops the frost alarm:
•
The outdoor temperature stays above the set unfreezing temperature for the
set time period.
Setting of the frost alarm:
You can reach the frost alarm settings by pressing the buttons:
First set when the frost alarm should be triggered. Use the arrow keys to adjust the out-
door temperature that must be undercut to trigger the frost alarm (e.g. 2.0°C).
Then set how many hours after precipitation the standby for the frost alarm should be
active (e.g. 5 hrs). Choose the standby period so that all humidity of the previous pre-
cipitation has dried.
Then set the conditions for the end of the frost alarm. Set the outdoor temperature to
be exceeded (e.g. 5.0°C) and the duration for which it should be exceeded (e.g. 5 hrs).
Choose the time period so that ice is completely melted thereafter.
The
Off
button lets you deactivate the frost alarm for all shades and windows.
Confirm your setting with the
OK
button.
Automatic
Settings
Frost Alarm
System
General
Settings