Device description 

elrest 

Automationssysteme GmbH 

e

VISIO PTE715_Windows.EN 

Page: 16 

 

2.1.5

 

Required  space 

With assembly in a switch cupboard, please ensure sufficient access to the device for the operator and 
maintenance work. 

Ensure a minimum distance of 80 mm from the back and circumferentially 50 mm. 

Care must be taken for sufficient air ventilation. 

 

 

 

 

 

 

 

 

 

 

 

Figure  1: Required space 

 

2.1.6

 

Mounting 

For easy front mounting, springs are mounted in the housing. 

With the springs can can be placed the device in the cutout and subsequently fixed in the mounting opening 
with the clamping blocks 

The spring clip mounting is not suitable for protection class IP54. Therefore, terminal blocks are required as 
an additional attachment for retrofitting and maintaining the IP54 requirement. (see chapte

„Dimension 

Drawing“

)

 

 

2.1.6.1

 

Number  of the  terminal  blocks 

 

Figure  2: Symbolic illustration 
Terminal block  for mounting

 

PTE715 aluminium:   

 

10 terminal blocks 

 

 

 

 

 

1 x MB225-3 set of terminal blocks (6 pieces)  

 

 

 

 

 

1 x MB225-8 set of terminal blocks (4 pieces) 

 

50 mm 

80 mm 

50 mm 

50 mm 

Содержание eVISIO PTE715

Страница 1: ...Device description eVISIO PTE715 V1 7 ...

Страница 2: ...al 13 1 10 3 Configuration 13 2 Implementing 14 2 1 Mechanical installation 14 2 1 1 Space requirement 14 2 1 2 Installation Assembly 14 2 1 3 Assembly Disassebly 14 2 1 4 Mounting position 15 2 1 5 Required space 16 2 1 6 Mounting 16 2 1 7 Disassembly 17 2 1 8 Dimension drawing 18 2 1 9 Dimensional drawings mounting cutout 18 2 1 10 Dimensions 18 2 2 Elektrical Installation 19 2 2 1 Supply voltag...

Страница 3: ... Gigabit Ethernet interface 30 4 3 4 LEDs for the Ethernet interface 31 4 3 5 X4 USB0 2 0 Host interface 31 4 3 6 S2 key SLEEP RESET 31 4 3 7 S3 key INT 32 4 3 8 Battery compartment 32 5 Software 33 5 1 General informationen 33 5 1 2 RTC Real time clock 33 5 1 3 Turn on 34 5 1 4 Login 35 5 1 5 Desktop 36 6 Maintenance and servicing 37 6 1 Maintenance 37 6 1 1 General 37 6 1 2 Changing backup batte...

Страница 4: ...Device description elrest AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 4 10 History 42 ...

Страница 5: ...rmany Phone 49 0 7021 92025 0 Fax 49 0 7021 92025 29 e mail vertrieb elrest de Web http www elrest de Technical Support Phone 49 0 7021 92025 33 Fax 49 0 7021 92025 29 e mail support elrest de This document was carefully created in order to ensure the correctness and completeness of the documentation Since in spite of all the care taken errors can never be completely avoided we are always grateful...

Страница 6: ...trations in this manual serve only as assistance for understanding the text Changes without references can be made We do not assume any liability for the correctness of the represented operations No claims for the modification of products that have already been supplied may be made on the base of the texts explanations and illustrations in this documentation elrest Automationssysteme GmbH takes on...

Страница 7: ...he relevant regulations VDE etc whilehandling electrical system are to be considered To activate Prevent unintentional restart The unit must be deenergized Ground and short circuiting No ground loops Cover or shield nearby live electric parts 1 4 Copyright Copyright 2017 elrest Automationssysteme GmbH in further consequence elrest mentioned all rights are reserved All parts of the software and the...

Страница 8: ...g danger which may result in damage to persons or property Indicates notes thereby the handling gets easier DANGER Personal injury caused by electric current Indicates a high risk imminently hazardous situation which if not avoided will result in death or serious injury DANGER Personal injury caused by electric current Indicates a high risk imminently hazardous situation which if not avoided will ...

Страница 9: ...nder voltage Always switch off the power supply before assembling the device eradicating defaults or carrying out maintenance operations DANGER Take note of the general regulations on prevention of accidents Take note of the relevant regulations on prevention of accidents e g the regulations during installation and commissioning of BGV A 3 electrical installations and equipment for mounting instal...

Страница 10: ... against materials which have creeping and insulating properties such as aerosols silicones and triglycerides found in some hand creams If it cannot be excluded that these substances are in the environment of the device incorporate the device in a cage which is resistant against the above named substances Always use proper tools and materials for the maintenance Table 2 Safty note ...

Страница 11: ...does not assume any liability for the transport risk If the carrier s liability of the transport enterprise does not cover the commodity value it is incumbenton the buyer to conclude an additional transport insurance The devices are delivered in a suitable packing To avoid damages please remove the packing before using the device If the packing includes further accessories or descriptions consider...

Страница 12: ...ng project is stored centrally in the master The ETHERNET based protocols and network variables supportcommunication In addition the terminals can also be operated on external products Notice Never exposing the device in a direct bright light source such as sunlight A small number of defective pixels in the display can occur despite state of the art production processes This is not a function rest...

Страница 13: ...e appropriate device if external measures are necessary for the minimization of the radiated interference Further the environment can affect the radiated interference Fulfils a device the higher engineer standards e g EN 61000 6 3 2007 generic standard emission Living quarters business and industrial areas and small enterprises it will be applied accordingly to the appropriate device see to chapte...

Страница 14: ... for maintenance work during the installation Ensure sufficient air circulation during installation 2 1 2 Installation Assembly The valid local and in particular electrical safety regulations must be kept Safety notes at the workplace The devices are intended for installation in switching cabinets The protection rating IP20 has to be warranted The installation point has to be in a solid position w...

Страница 15: ...FE All communication interfaces of the device have additionally be connected to the function earth FE in the communication plug if available The cable screens of the communication interfaces must be connected by the mating connectors with the FE The power supply 24 VDC must be in accordance with its requirements e g amount of all 24 V driver outputs adequately dimensioned and secured 2 1 4 Mountin...

Страница 16: ...are mounted in the housing With the springs can can be placed the device in the cutout and subsequently fixed in the mounting opening with the clamping blocks The spring clip mounting is not suitable for protection class IP54 Therefore terminal blocks are required as an additional attachment for retrofitting and maintaining the IP54 requirement see chapter Dimension Drawing 2 1 6 1 Number of the t...

Страница 17: ...E715 0 2 Nm Tighten the screws just so that the seal between the front and the mounting cutout is completely compressed and sealed Too strong and or uneven tightening of the screws can damage the device Only if all clamping bolts are used the tightness IP54 front can be achieved Overturning the screws can destroy the block Figure 3 Attaching of the brackets on the mounting plate 2 1 7 Disassembly ...

Страница 18: ...ension drawing Figure 4 Dimension drawing PTE507 2 1 9 Dimensional drawings mounting cutout Figure 5 Dimension drawing and mounting cutout 2 1 10 Dimensions Device A Height mm B Length mm C Depth mm D Length cutout mm E Width cutout mm PTE715 262 410 50 396 246 Table 4 Dimension of the device ...

Страница 19: ...SELV and PELV specifications The supply voltage may be intermediate within the specified voltage range Otherwise this may cause malfunction on the device See the technical specifications for the supply voltage requirements High frequency radiation from mobile phones for example can cause unintentional operating situations 2 2 1 1 2 2 1 1 Connectors for power supply For the connectors only use the ...

Страница 20: ...d to avoid electrostatic influences ETUC ESD Cables only plug in off when the device is turned off During the operation all connected cables must be connected to a remote peer 2 2 3 Connection to other elrest master devices For the Ethernet interface X2 can be used commercial RJ45 plugs 8 pol of good quality High quality CAT V cables are recommended Establish the connection as follows Order number...

Страница 21: ... voltages that are below the limit of human perception This kind of voltages occurs when somebody which is not electrostatically discharged touches a module chip component In most of the cases the components exposed to such overvoltages can not immediately be detected as defective Only after long operating of the device may an error occur An installation that conforms to EMCrequirements as well as...

Страница 22: ...le including all standard types of plastic desk top and clothes with synthetical material and so on Components must only be placed on conductive surfaces table witg ESD layer ESD conductive cellular material ESDpackaging ESD container Do not place the components near visual displays and monitors or television sets Keep a minimum distance of 10 cm 2 2 5 Guidelines The conformity of the above specif...

Страница 23: ...f delivery serial number index year of delivery Der Index Vx x yy teilt sich hierbei auf in x x Hardware status yy Software status Figure 7 Label WARNING Note for devices with the index PROTOTYP Prototypes are used only for test purposes Currentunit version Hardware Software Prototype Prototypex 0 yy Prototype 0 yy Pilot series V0 x yy Pilot series yy Series V1 x yy Series yy SN 2200707 V1 0 01 I0...

Страница 24: ...ntrol panels with integrated PLC LINK Compact PLC systems with integrated WEB server LINK Robust PLC systems with high performance degree of customization LINK 3 1 Communication interfaces Interface to all periphal units as stick keyboard printer a s o Ethernet With Ethernet can TCP Modbus as UDP or TCP be used on the base of socket functions can be additioned further protocols Table 5 Overview co...

Страница 25: ...Device description elrest AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 25 4 Device descriptions 4 1 Technical data ...

Страница 26: ...Device description elrest AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 26 ...

Страница 27: ...re are relationships between the storage temperature and the humidity Field Example Relative humidity Ambient temperature max 1 85 70 C In conditions of relative humidity of more than 90 can the device be stored at a maximum temperature of 70 C 2 60 60 C In conditions of storage temperatur of 60 C a maximum relative humidity of 60 is be allowed ...

Страница 28: ...USB0 Type A 2 X2 Gigabit Ethernet interface X2 100 1000 BASE T RJ45 with 2 integrated LEDs 3 S2 SLEEP Taster S2 Sleep Reset function 4 S3 INT Taster S3 Actually no function 5 Functional earth FE Functional earth FE 6 X1 Power supply X1 System power supply 24 VDC 7 Battery compartment Changing thebackup battery Battery compartment for Varta LithiumCR1 2 AA 3V Table 1 Legend for the rear view 1 2 6 ...

Страница 29: ...r supply of the safty class SELV PELV The system automatically switches off below the minimum voltage approx 16V Power supply X1 PIN Allocation Function Figure 9 X1 Power supply 1 2 3 24VDC 0 VDC FE Power supply 18VDC 30VDC Imax 1A GND Reference potential ground Function earth 4 3 2 Function earth FE Notice The PTE507 must be integrated into the grounding concept via its function ground FE connect...

Страница 30: ... White green 4 BI _D3 Bi directional Blue 5 BI _D3 Bi directional White blue 6 RX _D2 Receive Data Green 7 BI _D4 Bi directional White brown 8 BI _D4 Bi directional Brown A cross over cable with appropriate connection must be used for connecting the PTE Ethernet interface without a hub to a further Ethernet interface It is important that the wire pairs are configured as shown on the left 4 3 3 1 T...

Страница 31: ...s executed as a USB 2 0 Host interface with Type A socket Power supply can be max 500 mA for each interface and is protected by overcurrent detection The connection for this interface acc the USB specification 2 0 High Speed max transmission rate 480 MBit s The cable length must be 3 m The follwing table and illustration shows the pin assignment of this interface Interface X4 PIN Allocation Functi...

Страница 32: ...emeGmbH eVISIO PTE715_Windows EN Page 32 the device will be restarted during the Warm Boot phase 4 3 7 S3 key INT Currently the key has no function 4 3 8 Battery compartment The detailed use is described in the chapter Changeing buffer battery ...

Страница 33: ...The device can be operated via the following Touch operation Virtual keyboard Inputs via USB devices e g keyboard and mouse 5 1 2 RTC Real time clock The product has a clock for internal timer use The clock continues to run for at least 35 days after switching off the power supply at 25 C This can be set in system settings or BIOS 5 1 2 1 Capacitive Touch Tip and sharp edged objects can damage the...

Страница 34: ...e description elrest AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 34 5 1 3 Turn on The device is connected to the power supply via X1 After several seconds the homescreen appears Figure 14 Homescreen ...

Страница 35: ...AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 35 5 1 4 Login The user name is displayed and the password can be entered in the white field below The default setting on delivery for the password is demoipc Figure 15 Login ...

Страница 36: ...Device description elrest AutomationssystemeGmbH eVISIO PTE715_Windows EN Page 36 5 1 5 Desktop After the Login the desktop will be displayed The default IP Settings is DHCP Figure 16 Desktop ...

Страница 37: ...installed The battery ensures if the power supply is interrupted the internal clock continues to run The lifetime of the battery is approx 3 years under normal operating conditions Please use only a VARTA CR 1 2 AA Lithium this is a 3V battery with 970mAH Sources of supply The battery can be obtained from elrest AutomationssystemeGmbH Requirements The battery should be replaced within 10 minutes T...

Страница 38: ...y result in a risk of explosion Never load Do not open Do not short circuit Do not reverse polarity Do not heat above 100 C Protect from direct sunlight Do not allow moisture to condense on batteries In the case of a necessary transport the dangerous goods schedule for the relevant carriers labeling obligation has to be complied Used lithium batteries have to be dumped in the hazardous waste They ...

Страница 39: ...ce failure The PTE was checked before delivery and left the house in perfect condition Should an error occur you can find on our homepage Service Return Services the RMA form Please fill it out and send it to us We will attend immediatly 6 1 6 Accessory Designation Order number Comment Patchkabel RJ45 zu RJ45 commercially Connection to master devices Terminal block PTE715 MB225 3 and MB225 8 6 pie...

Страница 40: ...ur hotline with the following times Mon Fri 8 00 12 00 and 13 00 16 30 Phone 49 0 7021 92025 33 We offer education or project based workshops for the elrest products Besides you can of course always contact us by mail or fax Please contact our sales deparment for further information Fax 49 0 7021 92025 29 e mail support elrest de Phone 49 0 7021 92025 0 Fax 49 0 7021 92025 29 E mail vertrieb elres...

Страница 41: ...drawing and mounting cutout 18 Figure 7 Connection to other elrest master devices 20 Figure 8 Label 23 Figure 9 Rear view of the interfaces 28 Figure 10 X1 Power supply 29 Figure 11 X2 Ethernet 30 Figure 12 LEDs X2 31 Figure 13 LEDs X2 color 31 Figure 14 X4 USB interface 31 Figure 15 Homescreen 34 Figure 16 Login 35 Figure 17 Desktop 36 9 List of tables Table 1 Symbolics 9 Table 2 Safty note 10 Ta...

Страница 42: ...Gerätebeschreibung elrest AutomationssystemeGmbH eVISIO PTE5xx PTE7xx DE Seite 42 10 History Date Name Chapter Changing 08 08 2017 Hm all Created ...

Страница 43: ...ustrations descriptions dimensions and technical data correspond to the conditions or intentions at the time of printing of this brochure The company reserves the right to make any changes particularly where such changes are the result of technical development more economic design or similar factors Customers are solely responsible for the external connection of the devices Do you have questions r...

Отзывы: