AIR-CONDITION POWER SUPPLY ON/OFF CONTROLLER - ST100AC 

ST100AC controller is suitable for use in hotels, pensions and guesthouse rooms where air-condition switching off on window/door opening is 
not installed. With ST100AC and wireless CTX magnet window state detector installed, air-condition unit operation will be automatically on/off 
controlled depending on close or open state of windows or doors. The detectors are installed on windows or doors wings and are programmed 
to the controller. If window or door is opened for airing or other purpose, the CTX detector wirelessly notifies the controller which sets the air-
condition  unit  OFF  (cuts  off  mains  power  supply).  As  soon  as  the  window  or  door  closed  state  is  returned,  the  CTX  detector  notifies  the 
controller which sets the air-condition unit ON (mains power supply is set ON). ST100AC controller supplies 230VAC mains voltage at relay 
output and can operate with up to 16 wireless CTX detectors simultaneously. Radio transmission notification from CTX detector to ST100AC 
controller is protected by 

KEELOQ®

 hopping code encryption technology allowing high code security and error free communication. 

System Operation. 

The opening of one or more windows protected by magnet detectors CTX cuts OFF air-condition unit power supply. Power supply setting ON 
again  is  done  as  soon  as  all  installed  magnet  detectors  will  detect  all  windows  shut.  The  controller  remembers  open  or  shut  state  of  all 
windows in case of power supply cut off. On power supply return the controller will reinstate open or shut windows state as it was before the 
power supply cut off and consequently, will set the air-conditioning on or off. If, during the power supply cut-off period, a window was shut or 
open then it will be necessary to once open-shut the window to update window status memory of the controller. 

Jumper JP1 options. 

Setting OFF jumper JP1 results that the controller is neglecting any short time (less than 16 seconds) opening of protected window/s or door/s 
and should be off in standard operation. In that case, power supply to the air-conditioning unit will not be set OFF. If jumper JP1 is ON, the 
controller will switch off air-conditioning unit immediately on any window/s or door/s opening. 

Service RS switch. 

If  signal  from  magnet  detector  is  not  received  by  the  controller  due  to  detector  failure,  detector  loss  or 

detector’s  battery  failure,  pressing 

momentarily the RS switch resets the controller to 

“all windows shut” state and air-condition unit will be switch ON. 

Service OP and CL switches. 

Pressing  service  switches  OP  (open)  or  CL  (close)  executes  the  air-condition  unit  momentary  (as  long  as  switch  is  pressed)  power  supply 
setting to OFF or ON respectively, neglecting current window/s or door/s state. 

Jumpers JP2 and JP3. 

These jumpers are not used. 

Programming CTX detectors the controller.  

Up to 16 wireless magnet CTX detectors can be programmed (learned-in) to the ST100AC controller following procedure described below: 

a) Press shortly PRG button switch in the controller: the controller’s LED lights on steady after button release. 

b) Close or open window with CTX detector to be programmed or, move magnet in and out of the CTX case on the side of battery if detector is 
not  installed  yet

: controller’s LED starts  several blinking confirming end of  procedure. Not blinking LED signals programming error and the 

procedure should be repeated. 

Deleting  all  CTX  detectors 

in  controller’s  memory:

  To  delete  all  CTX  detectors 

in  the  controller’s  memory  press  and  hold  down  PRG 

switch  button  in the controller  as  long  as 

detector’s LED starts blinking (over 8 seconds) and then release the button.  Further blinking LED 

confirms cleared memory of the controller. 

It is not possible to delete one of many detectors in controller’s memory. 

 

Installation.

 

ST100AC controller should be installed in safe and dry place. No external antenna is needed in standard same room operation with CTX 
detector/s. If needed, an external 17 cm long wire antenna should be installed to A marked terminal and let loose downwards (not glued or 
fitted to wall). Care should be taken not to expose the controller to harsh 
environmental conditions or high humidity. 

Description of ST100AC  controller wiring terminals:

 

 

L

 

– controller 230VAC mains supply 

LIVE 

wire terminal, 

N

 - controller 230VAC mains supply 

NEUTRAL

 wire terminal, 

PE

 - controller mains supply 

GROUND 

wire terminal,  

PE

 

– air-condition unit  

Ground

 wire terminal,  

Lo

 - air-condition unit  mains supply 

LIVE 

wire terminal, 

No

 - air-condition unit  mains supply 

NEUTRAL 

wire terminal. 

WARNING! Switches OP, CL and RS must never be 
connected to any voltage! 

Specification

 

  mains supply 230VAC controller with receiver for 433,92MHz band,  

  relay outputs for air-condition unit max 16A/230VAC (2.5 kW), 

  indoor operation only with temperature from 0 up to +50 deg. Centigrade, 

  control panel external dimensions (l/w/h) 87/87/39mm,

 

  wireless open field operating range: up to 100m.

 

Manufacturer: 

ELMES ELECTRONIC, 54-611 Wroclaw 

– PL, 

Avicenny Str. 2, phone (+48) 71-784-59-61, fax (+48) 71-784-59-63

 

 
Manufacturer’s Limited Warranty: 

Elmes Electronic products 

carry two year manufacturer’s warranty as from date of purchase. The warranty is limited to the replacement of 

faulty original parts or repair defects of improper manufacture. Damage, faulty use or improper handling by the user or installer as well as any 
changes in product’s hardware or software caused by the user violets the warranty and all due repair costs will be charged. Elmes Electronic 
shall not be responsible for any damage human or material caused by its products failure to operate correctly. 

elmes