ELEMENT Defines
the power system
configuration
STAR /DELTA/
SINGLE PHASE
IPh (
)
Programming
Parameter
Default
Option/Range
PT Primary
100V-999kV To set 11kV Set first
four digits (1100) as explained
above. Press
key to
Up / Down
place decimal point at appropriate
location. LED K will indicate Kilo
3.4 Display
PT Secondary
50V - 550V
CT Primary
0.5A - 99KA
CT Secondary
0.5A - 6A
www.elmeasure.com
3.1 Programming Keys
Press +
to enter setup mode .
Up
Down
Enter Password
blinking of digit indicates Edit is possible.
(default 1000)
Press
to decrement value from 9 to 1.
Down
Press to move to the next digit till 4th digit .
Up
If Password is correct, editing is possible.
Enters into clear mode and meter displays CLr.l (Refer 3.3A).
(Refer 3.3B
for
).
only
6400
Press
key to view and press
key to edit.
Down
U
p
Press
to decrement values or to select from available options.
Down
Press to save the value / parameter.
Up
Press
to edit next parameter till end of last parameter &
Down
display screen will prompt display reads (YES).
Press
to change to (NO) .
Down
Press to save.
Up
To decrement
value
To select / Edit &
save Value
3.2 Setup Procedure
Ph: +91 639-1010-320
HO & Unit -1 :
47-P, Hardware Park,
,
KIADB
- 562149
Huvinayakanahalli Bengaluru
Karnataka INDIA.
Sales Offices :
BENGALURU CHENNAI COIMBATORE MUMBAI DELHI HYDERABAD USA UAE
Unit -2 :
Goutham Garden, No.4,
,
Veerapandi Coimbatore - 641 019
Tamilnadu INDIA
PG/ 3R /V / 1
LG N 1 9 9
0
True RMS measurements.
Simultaneous sampling of voltage and current.
STAR, DELTA and 1PHASE Programmable wiring connections.
Universal Auxiliary supply 80 - 300V AC/DC.
Auto Scaling of Decimal point and Auto scrolling.
Old register to store previously cleared Energy values.
Programmable CT & PT Ratio.
Bar graph programmable for Amps/Watts/VA
User programmable password protection.
Energy Import and Export, number of interruptions available.
Individual Phase energy through communication.
Demand measurement for watts, VA & Var (only for LG 6400).
THD measurement upto 15th harmonics.
3-Row 12-digits display with unique look.
Individual phase angle measurement.
3.3A Clear Mode : Clear Integrator
Press key
Up
Press
Key
Down
Press key
Up
Press
Key
Up
Press key
Up
to accept the edited
option
3.3B Clear Mode : Clear Demand
Meter displays CLr.I. ‘n’
(with n is blinking)
Option : (YES)/(NO)
‘y’(for clearing )
‘n’ (for not clearing)
Meter displays CLr.M.
Displays CLr.M options
‘n’
can be changed by pressing
Down
Key. Display will
‘y’
‘n’
prompt to (or) while
pressing
key.
Down
Comes back to Default page
(Clear Mode ends here)
Option : (YES)/(NO)
‘y’(for clearing )
‘n’ (for not clearing)
Press
key to
Up
accept the edited
option
Comes back to Default page
(Clear Mode ends here)
Meter displays CLr.M
Displays CLr.I
options
‘n’
can be changed by pressing
Key. Display will
Down
prompt to (or)
while
‘y’
‘n’
pressing
key.
Down
Value Indication
Percentage Load
Communication
To view the parameters
Downwards.
To
parameter
view the
s Upwards.
Minus
Mega
Kilo
Pulse
Phase angle
Export
Energy
Maximum
Demand
Total harmonic distortion
LG 6400 LG 6445
LG 6435 LG 6425
LG 64xx
Parity (PrtY)
Odd/ no(none)/EVEn
VA selection(UA.SL)
Vector. harmonic/Vector/
Arithmatic.
Baud rate (bA )
Ud
2400/
/9600
4800
/19.20k
/38.40k
Energy value format
Selection(ENEr)
COUN (Counter) / RESL
(Resolution)
Password
1000 - 9999
Device Id (dU. )
Id
1.000 247.0
-
Range: 50ms to 500ms
Pulse output On
time
1. FEATURES
2. KEY & DISPLAY INDICATION
3. PROGRAMMING MODE