27.6 Vdc  5 Amp Switch Mode Power Supply for Fire – EN54-4:1997 +A1 +A2 

STX2405-E   
STX2405-C 

 
 

F

EATURES

 

 

 
The STX2405-x is an EN54-4:1997 +A1 +A2 approved power supply ideal for use in Fire and Smoke and 
ventilation control Systems. Its regulated 27.6V dc output will supply up to 5 Amps continuous into 
the load, in addition to providing up to 850mA for charging the standby batteries up to 17Ah. The 
power supply output features electronic short circuit protection under both mains and standby 
battery operation. Maximum battery life is assured through continuous active battery monitoring and 
the use of a two stage charger, comprising bulk and temperature compensated final float phase 
depending upon battery condition. Once fully charged the product operates in Eco power saving 
mode, whereby the batteries are charged for 4 hours in every 24 hour period while still being 
continuously monitored. This reduces wasted energy in charging already fully charged batteries and 
extends their working life. Deep discharge protection prevents premature battery failure when 
operating from standby for extended periods. Two sets of volt free solid state relay fault output signal 
(i) loss of mains and (ii) battery fault, charger fault and loss of output. In addition there is an optional 
plug in serial interface that can provide diagnostic and fault reporting information to supervisory 
systems.  
 

 

Certified by UL to EN54-4:1997 +A1 +A2. 

 

Up to 5A current to load at 27.6V dc nominal regulated output. 

 

Charging capability to support 7 or 17/18Ah batteries. 

 

Electronic overload protection shuts down output until overload or short circuit is removed. 

 

Battery Monitor detects battery missing, low battery, short-circuit or reverse connection or circuit 
impedance (Ri) in excess of 500m

 caused by connector or wiring  corrosion within 4hours. 

 

Battery charging circuit is energised only when a battery is correctly connected and the battery voltage 
is greater than 14 V. 

 

No loss of output during automatic connection of battery to load on loss of mains. 

 

Deep discharge protection disconnects battery from load when battery voltage falls below 21 V. 

 

Diagnostic indicator LED (Orange) (Internal). 

 

Fault indicator LED (Yellow) flashes on detection of output fault, battery fault, charger fault and mains 
failure. 

 

Mains indicator LED (Green) showing mains present Indicators check at start-up. 

 

Optional RS232 serial interface for fault reporting and diagnostics. 

 

                

 

 
Elmdene International Ltd

 

 

Tel:  +44(0)23 9269 6638 

3 Keel Close, Interchange Park, 

 

Fax:  +44(0)23 9266 0483 

Portsmouth, Hampshire, PO3 5QD, UK 

Web:   

www.elmdene.co.uk

 

0843-CPR-0215 

14 

Содержание STX2405-E

Страница 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Страница 2: ...Sonic model Yuasa model Interlogix model 2 x 2 1 Ah 12 V PS12021 NP2 1 12 2 x 7 Ah 12 V PS12070 NP7 12 2 x 17 18 Ah 12 V PS12170 NP17 12 BS131N Battery Charging Constant current bulk charging to 80 ca...

Страница 3: ...le Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None No fault OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present...

Страница 4: ...the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed from a mains...

Страница 5: ...when loaded Ensure that wall fixings are appropriate to support this weight The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if i...

Страница 6: ...ashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and GEN PSE Fault outputs to the appropriate inputs of...

Страница 7: ...tor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 18 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact...

Страница 8: ...an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal fa...

Отзывы: