ELK-6050 Wireless Smoke Detector

Page 1

ELK-6050

Wireless Photoelectronic Smoke Detector with
built-in rate-of-rise and fixed temp Heat Sensor

For the latest downloadable version of this manual visit our website: http://www.elkproducts.com

Installation Instructions

Applications and Overview

The ELK-6050 Wireless Smoke Detector is designed for use with Elk's
two-way wireless product line consisting of the ELK-M1XRFTW Trans-
ceiver and the ELK-M1 Control.  It is intended for residential and light
commercial applications and incorporates many features designed to
ensure its reliable performance.

The 6050 is powered by long life 3V Lithium batteries, providing power
to both the detector and the built-in wireless transmitter.

  The unit utilizes

photoelectric smoke detection technology, and also includes fixed
temperature 135°F heat detection and rapid "rate-of-rise" temperature
detection.  Built-in self-diagnostics monitors sensitivity and operation
status. Should the unit drift out of the UL Listed sensitivity range or fail
the internal diagnostics, it will extinguish its Alarm/Status LED and signal
a trouble condition to the Control.  

This detector meets NFPA 72 field

sensitivity testing requirements without the need for external meters. A
sensitivity test feature provides visual indication of the sensitivity level
and warns if service is required.  Built-in drift compensation allows the
product to adjust sensitivity automatically as it becomes dirty over time.
The drift compensation feature dramatically increases the time between
cleanings, as well as reducing the chance of nuisance alarms.

Specifications

Operating Voltage:

3 VDC

Average Standby Current:

10 µA

Maximum Alarm Current:

30 mA

Battery  Type:

3V Lithium x 2, Panasonic CR123A,
Duracel DL123A   (meets UL minimum 1
year life expectancy requirement)

Smoke Detection:

Photoelectronic

Sensitivity:

.88% to 3.63%/ ft.

Heat Detection:

Fixed 135°F ± 5°F (57.2°C ± 2.8°C)
Rate-of-Rise 

15°F/min>105°F (8.3°C/

min>

40.6°C)

Built-in Sounder:

85 dBa at 10’ temporal pattern

Battery Trouble Threshold: 2.75V
Low Battery Beep Rate:

1 every 45 seconds.

Wireless Freq:

902 Mhz - 928 Mhz frequency hopping

Maximum wireless range: 200 feet
Dimensions:

5.6" x 2.4" (14.2cm x 6.1cm)

Operating Temperature:

40 to 100°F (4.4 to 37.8°C)

Operating Humidity:

0 to 95% non-condensing

Agency Listings:

UL268

About This Guide

This Guide describes the installation, operation, and maintenance of this
product. Please read these instructions thoroughly prior to installation.

Installer:

 This document should be left with the owner/user.

Owner/User:

  Keep this document in a handy location and refer to 

it

when you have questions about this products functions or features.
Reading this guide is the only way to learn how to use your product
wisely and to know how to react in the event of an alarm.  

This product

is a member of a reliable, high-quality product family using the latest
technology available. Review the information in this section to
ensure you get the most out of the product. The information in this
User Guide is in accordance with NFPA 72.

Components List

Smoke Detector electronics assembly

Mounting Baseplate
Mounting Screws and Anchors
Two CR123A lithium batteries
This User Guide

Two-way Communications

When multiple ELK-6050 Smoke Detectors are installed and enrolled into
the same Control the two-way communications features offered by the
Elk wireless permit certain communications to flow in both directions.  For
example; whenever any 6050 Smoke Detector alarms and the alarm is
communicated to the Control, the Control will broadcast a signal to all other
enrolled 6050 Smoke Detectors informing them to turn on their sounder.
Likewise, whenever the alarm is silenced at the Control, a broadcast will
be transmitted to silence the other "like" detectors.  EXCEPTION: If smoke
is still present in a detector, that detector will not cease sounding until the
smoke has been cleared.  Below is a complete listing of the two-way
communications signals:

Alarm

- Sent from 6050 to the Control advising that the

detection chamber has sufficient smoke or heat to
qualify as an alarm condition.

Trouble

- Sent from 6050 to the Control advising that the

detector has an internal fault and may require
service.

L o w

- Sent from 6050 to the Control advising that the

Battery

batteries have reached a low voltage state and
must be replaced to maintain proper operation.

Test/Silence

- Sent from  6050 to the Control advising that the Test

Button was pressed on a detector.  Also used to
silence the alarm on that individual detector.

Sounder On

- Sent from Control to all enrolled 6050 Smoke Detectors

informing them to activate their sounder.

Sounder Off

- Sent from Control to all enrolled 6050 Smoke Detectors

informing them to silence their sounder.  This is
triggered by the silencing of the Fire Audible.  NOTE:
A detector will not silence if it continues to detect
smoke or heat.

Trouble Off

- Sent from Control to all enrolled 6050 Smoke Detectors

informing them to silence their trouble chirps.  In the
case of a low battery trouble chirp, if the batteries
are not replaced then the chirp will re-start after 24
hours.

Alarm/

Status LED

Heat Sensor

and  Ack  LED

Test/Silence

Button

Alarm
Sounder

Heat
Sensor

Содержание ELK-6050

Страница 1: ...This document should be left with the owner user Owner User Keep this document in a handy location and refer to it when you have questions about this products functions or features Reading this guide...

Страница 2: ...you may need to reference other chapters of NFPA 72 or NFPA 101 Inaddition observealllocalandnational building and electrical codes See back page for listing of NFPA Guidelines When choosing an insta...

Страница 3: ...personnel identify the sleeping quarters of these individuals IMPORTANT It is recommend that the Smoke Detector be enrolled added into the Control and a Full Test be performed prior to permanently mou...

Страница 4: ...r s Test Silence button but down inside the cavity where the heat sensor is located This LED helps provide a way to verify that the wireless RF communications to the Control The LED will briefly flash...

Страница 5: ...lowed before a sensor is declared missing 9 PROGRAMTHEZONEDEFINITION ThismustbedonefromKeypad Menu 5 Zone Definitions for all new enrolled wireless zones Program the zone definition of the 6050 detect...

Страница 6: ...If error persists replace smoke sensor 4 7 Smoke sensor is within normal sensitivity range None 8 9 Smoke sensor is becoming too sensitive Verify smoke chamber is snapped down securely Clean smoke se...

Страница 7: ...total coverage shall include all rooms halls storage areas basements attics lofts spaces above suspended ceilings and other subdivisions and accessible spaces and the inside of all closets elevator sh...

Страница 8: ...how two exits from each room It is important that children be instructed carefully because they tend to hide in times of crisis o Establish one meeting place outside the home Insist that everyone meet...