FC BASIC
Electronic Fan-Coil Controller
<IMG INFO> 340,05
Страница 1: ...FC BASIC Electronic Fan Coil Controller IMG INFO 340 05...
Страница 2: ...n algorithm 15 5 1 1 Utility control 15 5 2 Regulation algorithm in Heating Cooling mode 16 5 2 1 REGULATION ALGORITHM IN COOL MODE 16 5 2 2 REGULATION ALGORITHM IN HEAT MODE 17 5 2 3 REGULATION ALGOR...
Страница 3: ...re described in more detail If the online Help on the PC is used the words in italics become proper hyperlinks automatic links activated by a click of the mouse that connect the different sections in...
Страница 4: ...he panel is used to adjust the set point and two slider switches are used to set a the mode for Interface F1 heating off cooling for Interface F2 on off b the fan speed low medium high Some models als...
Страница 5: ...is far from setpoint 2nd step electric heaters in integration 2 2 Available models 14 versions of FC Basic are available with different operating features summed up in the table below Table of models...
Страница 6: ...anual change over Automatic change over Outputs water valve H or C x x x H and C x x x Electrical Resistors Electric H x x x Thermo regulator H C Y Y Dead Zone Y Y Hot Start driver Timer Temperature W...
Страница 7: ...shocks Ongoing exposure to jets of water under pressure Exposure to aggressive polluting atmospheric agents which could cause corrosion or oxidation such as sulphuric or ammoniac substances salt mists...
Страница 8: ...50C 110C 10C 70C ST2 NTC sensor input air temperature This is the temperature control sensor It is always integrated on the PCB but can be an additional remote sensor positioned in the return air flo...
Страница 9: ...eam of the valve and as close as possible to the battery On a 4 pipe system it must always be mounted on the hot water circuit never on the cold water circuit 3 5 Digital outputs Digital outputs consi...
Страница 10: ...h INTEGRATED AUTOMATICALLY ADJUSTING electric heaters the HOT function is not available The Dip Switch default setting factory pre set is the following DIP nr Description On Off default factory pre se...
Страница 11: ...ate from the main interface by using a tiny screwdriver Insert the screwdriver into the appropriate holes at the side of the housing wrest gently till both parts are separated 2 Before proceeding with...
Страница 12: ...n the Dead zone Blinking indicates that regulation algorithm has not been satisfied but consent by the water sensor is not being given to start the fan Stays on cooling is available fan and valve acti...
Страница 13: ...t speeds AUTO AUTOMATIC Dynamic operation in the following modes HEAT COOL STAND BY condition Summer Winter on the basis of comparison of water temperature with set point setting OFF dead zone dependi...
Страница 14: ...onsent in HEAT mode consent to valve and fans at water temperatures above 30 C the switch to COOL is explained below with relative changes to consents water temperature C 15 C 30 C COOL MODE VALVE MOD...
Страница 15: ...iversal models dip switch 2 specific models 5 1 1 Utility control Operating modes heat cool are affected by the consent to the water sensor if present for 2 pipe system models If both water heating an...
Страница 16: ...xplanatory diagrams below 5 2 Regulation algorithm in Heating Cooling mode 5 2 1 REGULATION ALGORITHM IN COOL MODE Regulation algorithm in cooling mode OFF cool raff set point room temp temp ambiente...
Страница 17: ...FC BASIC User Manual 17 24 5 2 2 REGULATION ALGORITHM IN HEAT MODE Regulation algorithm in heating mode OFF heat risc set point room temp temp ambiente C hysteresis isteresi...
Страница 18: ...e temperature Dead Zone Setting depends on water temperature as shown in the following three examples N B There is a fixed hysteresis of1 C between temperatures of 15 C and 30 C to prevent constant fl...
Страница 19: ...together with the temperature controller in heating mode winter EXAMPLE C The temperature of the water is sufficient to transfer heat the electric heaters more cost intensive are a second option temp...
Страница 20: ...ter sensor the red LED heating will Blink After the delay when the fan starts the red LED will illuminate continuously This function is only enabled in heating mode The temperature driven Hot start fu...
Страница 21: ...le on all models with product codes having suffix E or N The Yellow LED will Blink when the ECO mode is operational 6 8 Window contact Through a window contact voltage free connected onto analogue inp...
Страница 22: ...Storage humidity non condensing 30 90 10 Digital outputs rating 230V 5 2 A Analogue inputs 1 1 NTC probes Assembly wall mounted Housing colour Front white Base plate grey Connections screw terminals...
Страница 23: ...ailure to comply with the safety instructions specified by applicable regulations and or provided in this document use with equipment which does not provide adequate protection against electric shocks...
Страница 24: ...INTRODUCTION 4 L LED s 12 M Manual change over 13 Mounting 7 O Operating mode slider 12 Operating modes 13 Operating modes table 13 P Periodic ventilation 20 Permitted use 23 Post Ventilation 21 R Ran...
Страница 25: ...FC BASIC User Manual 25 24 FC BASIC User Manual 2006 9 Cod 8MA10103...