Appendix
2: ELCORplus version for Zone 2
186
2 Safety
2.1 General
The device
ELCOR
plus
for Zone 2
is approved according to Directive 2014/34/EU (NV
No. 116/2016 Coll.) and has been released with the following certificate:
FTZÚ 19 ATEX 0002X
Certificate of examination certificate (ATEX) for use in
potentially explosive atmospheres.
Important Notice:
ATTENTION!
The device is designed according to safety principles for use in potentially
explosive atmospheres of type Zone 2.
It is approved as a safe device with combined protection of the type
"intrinsic safety" ic and a type of non-sparking device "nA" according to the
standards EN 60079-0, EN 60079-11 and EN 60079-15.
The version for Zone 2 must not be used in Zone 0/1, otherwise, there is a
risk of explosion.
DANGER!
The device must be installed and used in accordance with this documentation and
the conditions specified in the ATEX certificate.
Warning!
The specified protection IP66 is only valid if cables of suitable diameter and
proper tightening are used in the cable glands of the device. Unused cable glands
must be blinded. Unused cable glands must be blinded.
2.2 Use in potentially explosive atmospheres zones
Based on Certificate of Examination type 19 ATEX 0002X, the device can be operated in a
potentially explosive atmosphere designated Zone 2 (space in which an explosive gaseous
atmosphere is not likely to occur during normal operation, but will remain for a short period of time
if this atmosphere occurs) – EN 60079-10-1).
Содержание DATCOM
Страница 38: ...3 Technical Parameters 36 ...
Страница 45: ...5 Installation and Commissioning 43 5 1 2 ELCORplus corrector Fig 2 ELCORplus device dimensions ...
Страница 50: ...5 Installation and Commissioning 48 Fig 7 Examples of data plates ...
Страница 83: ...5 Installation and Commissioning 81 Fig 37 Communication via RS232 RS485 using B RS module ...
Страница 115: ...7 Technical Description of the Device 113 Fig 57 Functional diagram of ELCOR ...
Страница 116: ...7 Technical Description of the Device 114 Fig 58 Functional diagram of ELCORplus ...
Страница 122: ...7 Technical Description of the Device 120 Fig 61 Modem replacement ...
Страница 139: ...7 Technical Description of the Device 137 Fig 65 Volume and energy calculations calculation scheme ...
Страница 159: ...10 Communication with the Device 157 packet ...
Страница 174: ...12 Accessories 172 Fig 78 ELCORplus example of use of external modules ...
Страница 175: ...12 Accessories 173 Fig 79 ELCOR example of use of external modules Fig 80 ELCOR example of use of external modules ...
Страница 211: ...Appendix 2 ELCORplus version for Zone 2 209 Fig 86 Block diagram ELCORplus for zone 2 with ext 230V power supply ...
Страница 213: ...Appendix 3 Compass Data Export 211 Preview of generated document ...