Sorensen DCS Series 3kW Supplies
Advanced Operation
4.7
4.7.1
Using Multiple Supplies
DCS Series power supplies of the SAME MODEL may be operated with outputs in series or in
parallel to obtain increased load voltage or increased current. Split supply operation allows two
positive or a positive and a negative output to be obtained.
Configuring Multiple Supplies for Series Operation
Series operation is used to obtain a higher voltage from a single output using two or more
supplies. Connect the negative (-) output terminal of one supply to the positive (+) output
terminal of the next supply. See
. The total voltage available is the sum of the
maximum voltages of each supply (add voltmeter readings). The maximum allowable current for
a series string of power supplies is the model-rated output current of a single supply in the
string.
Note:
The maximum allowable sum of the output voltages is 600 Vdc. This is limited by the
voltage rating of certain internal components.
CAUTION
Remote sensing must not be used during series operation.
CAUTION
The remote programming input is internally referenced to the supply's negative
output. Do not connect remote programming input lines (J3 pins 9 and 10) to
the supply's positive output.
Figure 4-22 Series Operation of Multiple Supplies
(Local sense lines shown are default J3 connections.)
Operation Manual
4-21