Static electricity meter 

 

GAMA 100 

G1B.xxx 

 

 

 

 

 

 

 

 

 

User manual 

Version 2.3b

 

 
 

(G1BEN23b) 

 
 
 
 
 
 
 

 

 
 

“ELGAMA – ELEKTRONIKA” Ltd., Lithuania 2016 

Содержание G1B Series

Страница 1: ...Static electricity meter GAMA 100 G1B xxx User manual Version 2 3b G1BEN23b ELGAMA ELEKTRONIKA Ltd Lithuania 2016...

Страница 2: ......

Страница 3: ...ELGAMA ELEKTRONIKA Static electricity meter GAMA 100 G1B xxx USER MANUAL ELGAMA ELEKTRONIKA Ltd 2 Visori str LT 08300 Vilnius Ph 370 5 2375000 Fax 370 5 2375020 E mail info elgama eu...

Страница 4: ...irmware upgrade functionality was added 2 1 2014 04 29 Description of internal PRIME PLC modem modification H2 and firmware upgrade functionality was added 2 2 2015 03 04 Tariff program update LCD lis...

Страница 5: ...Construction 16 5 1 Case 16 5 2 Nameplate 16 5 3 Terminal block 17 5 4 Operation principle 18 5 4 1 Measurement module 18 5 4 2 Signal conversion 18 5 4 3 Micro controller 18 5 4 4 Non volatile memory...

Страница 6: ...41 9 4 Under voltage monitor 41 10 Tariff program 42 10 1 Day tariff programs 42 10 2 Week tariff program 43 10 3 Tariff seasons 43 10 4 List of special days 43 10 5 Emergency tariff 44 10 6 Tariff t...

Страница 7: ...connect by end of event 59 14 8 Action connect by Menu button 59 14 9 Action connect by the mains switch of the internal electrical installation 59 15 Installation 60 Annex A Dimensions of the meter...

Страница 8: ...alling parameterization and verification can be performed only by authorized organizations that have qualified technicians Only qualified persons should install meters 2 Meter s connection or disconne...

Страница 9: ...check whether inputs are connected properly to terminal block 4 If meter calendar season season time name or valid tariff time zone does not correspond to real situation meter s parameterization data...

Страница 10: ...meters for active energy classes 1 and 2 IEC 62053 23 2003 Electricity metering equipment a c Static meters for reactive energy classes 2 and 3 IEC 62052 11 2003 Electricity metering equipment a c Gen...

Страница 11: ...able 3 2 Technical specifications Accuracy class Active energy measurement B EN 50470 3 1 0 IEC 62053 21 Reactive energy measurement 2 0 IEC 62053 23 Reference voltage Un V See Table 4 2 Operating vol...

Страница 12: ...meters with supercapacitor 40 T 70 C 3K7 25 T 70 C Storage transportation 40 T 70 C Mass kg 0 9 Dimensions mm with usual terminal cover with special terminal cover for GSM GPRS modem 180 x 130 x 65 s...

Страница 13: ...tuned to 50 Hz narrow band Total Harmonic Distortion THD for current and voltage is calculated by formulas 2 2 2 NB NB WB I I I I THD 2 2 2 NB NB WB U U U U THD IWB RMS value of current measured in w...

Страница 14: ...attery for old battery s replacement Disconnect old battery s connector remove the battery Place new battery into old one s location and connect plug to the corresponding meter socket Put in silicone...

Страница 15: ...ordering code and are listed in Table 4 10 Optional LCD display supports indication of up to 6 six tariffs Extended LCD displays OBIS code by means of 6 symbols while default LCD and optional LCD poss...

Страница 16: ...e possibility to touch the meter terminals with sealing wire while sealing the terminal cover is prevented Figure See Figure 5 1 presents meter exterior parts and allotment of control elements For cas...

Страница 17: ...mark number of the EC design examination certificate 13 The conformity marking CE and M number of notified body 5 Reference voltage current measuring range reference frequency 14 The class index of th...

Страница 18: ...rter Digital signal processor DSP calculates average power values P t and Q t as well as instantaneous RMS values of current and voltage Furthermore DSP outputs values of RMS current in neutral and el...

Страница 19: ...voltage of battery is to low and warns when battery has to be replaced 2 Index field Identifies measured data code OBIS code Explanation of OBIS codes for basic data can be printed on meter s namepla...

Страница 20: ...rinted on meter s nameplate 3 Communication indicator Indicates when communication operates via optical or electrical communication interface 4 Main value field Shows the measured value up to 8 digit...

Страница 21: ...riff field T1 T2 T3 T4 T5 T6 Shows current energy tariff only one segment is turned on Lit segment indicates active energy tariff blinking segment indicates active emergency tariff for energy 6 Billin...

Страница 22: ...ward MM00 hh Clock is adjusted for summer time on the last Sunday of a specified month on the time specified by winding the clock 1 hour forward Clock is adjusted for standard time on the last Sunday...

Страница 23: ...d voltage circuits are connected permanently Figure 5 8 Sliding voltage link connected 6 Communication The meter supports two way communication via various interfaces data reading at the request as we...

Страница 24: ...2 as well as fixed to DIN rail separately For more information please refer to modem s instruction Meter is equipped with RJ12 connector for easy controller connection Controller depends on his constr...

Страница 25: ...voltage power lines Please refer to official web site of the PRIME Alliance http www prime alliance org for further information Modem is based on chipset processor C2000 and analog front end AFE031 r...

Страница 26: ...sabled switched off by special configuration command This is usually carried out when meter is connected to AMI system by means of another modem e g GSM GPRS modem Table 6 1 Maximum self consumption o...

Страница 27: ...billing system for more than 24 hours or after every start up Plug Play function over PLC is ensured by means of PLC communication provider and data concentrator DMDC New meters in PLC network are reg...

Страница 28: ...cation of meter cover transparent or non transparent meters cover is used see Figure 5 1 and Figure 5 2 Meter with transparent cover have two additional push buttons sealed push button which located u...

Страница 29: ...Billing period energy Energy tariff number T 0T6 0 the sum of all tariffs 1 8 T A 1 9 T A 2 8 T A 2 9 T A 15 8 T A 15 9 T A 3 8 T R 3 9 T R 4 8 T R 4 9 T R 5 8 T R1 5 9 T R1 6 8 T R2 6 9 T R2 7 8 T R...

Страница 30: ...7 4 0 Q3 7 5 0 Q3 8 4 0 Q4 8 5 0 Q4 Demand values are displayed in kW in kvar for reactive demand with three digits after the decimal point see Figure 7 4 Furthermore demand value of current integrat...

Страница 31: ...m demand in tariff M Demand tariff number M 0T6 0 max demand off all the tariff zones Maximum demand is displayed automatically in three steps see Figure 7 5 1 maximum demand value 2 date of maximum d...

Страница 32: ...rameterization may be reviewed in meter s LCD All data stored in billing profile may be downloaded to computer via communication interfaces Values of billing profile are identified by OBIS code in met...

Страница 33: ...5 0 Instantaneous RMS current A in phase 15 8 0 A 91 5 0 Instantaneous RMS current A in neutral 3 8 0 R 15 5 0 Active power P kW 4 8 0 R 3 5 0 Reactive power Q kvar 5 8 0 R1 4 5 0 Reactive power Q kva...

Страница 34: ...tion period 8 4 Wired M Bus load profile The wired M Bus interface is employed to collect data from up to four multi utility water gas meters Electricity meter reads multi utility water gas billing da...

Страница 35: ...IS C 60 12 counts the number of occurrences 0T 9999 of over voltage events as well as a dedicated timer OBIS C 61 12 measures the total duration 0T99 999 999 s of all over voltage events Every entry o...

Страница 36: ...s the total duration 0T99 999 999 s of all Power over limit events Every entry of the log book is expressed as a string example for IEC 62056 21 P 98 20 ST Timestamp where event number ST status bits...

Страница 37: ...meter cover event log registers tampering attempts to open main meter cover Event log stores up to 60 entries i e up to 30 meter cover opening events open close Furthermore a dedicated counter OBIS C...

Страница 38: ...se constant changed 00000002 change baud rate password communication timeout 00000004 end billing period begin test mode end test mode change external relays state 00000008 change identification numbe...

Страница 39: ...eset log registers Load profiles resets of meter Each reset creates entry in the event log Entry contains date and time of event as well as status indicating type of reset Load profiles reset event lo...

Страница 40: ...ter 6 8 3 Relay output connects contacts from the beginning until the end of Power over limit event i e until the end of integration period Contractual power limit Plim is parameterized in W Watt unit...

Страница 41: ...as a dedicated timer measures the total duration 0T99 999 999 s of all over voltage events Limit values Uover and Uover hyst can be parameterized independently in V Volts units 9 4 Under voltage monit...

Страница 42: ...d season profiles may be set for energy tariffs and or demand tariffs independently It can be set or readout via all available communication interfaces 10 1 Day tariff programs Day tariff programs see...

Страница 43: ...n up to 12 tariff seasons Table 10 3 List of tariff seasons Season number Season start date Assigned week tariff program 1 01 01 1 2 02 01 3 3 03 01 2 T n 12 01 1 10 4 List of special days There are t...

Страница 44: ...rrent billing period 17 1 6 M VV Maximum demand P kW of tariff M 1T6 in previous billing period VV 18 1 8 0 Total energy A kWh current value 19 1 8 0 VV Total energy A kWh value at the end of previous...

Страница 45: ...Q kvar of tariff M 1T6 in current billing period 75 4 6 M VV Maximum demand Q kvar of tariff M 1T6 in previous billing period VV 76 4 9 0 Billing period energy R kvarh current value 77 4 9 0 VV Billi...

Страница 46: ...s 129 14 7 0 Frequency Hz 130 15 7 0 Instantaneous power P kW 131 16 7 0 Instantaneous power P kW 132 3 7 0 Instantaneous power Q kvar 133 4 7 0 Instantaneous power Q kvar 134 11 7 0 Instantaneous RMS...

Страница 47: ...0 9 Meter relays output state 198 F F 0 Error code 199 P 1 0 Load profile 200 P 97 0 Power failure outage event log 201 P 98 12 Voltage swell Over voltage event log 202 P 98 13 Voltage sag Under volta...

Страница 48: ...s LCD control commands and scroll push button Before proceeding further let us remember LCD control commands short signal Light signal with duration of 2 s or push of the scroll push button for 2 s lo...

Страница 49: ...constants Initial parameterization is performed while meter is assembled and while major repairs of the meter Initial parameters are presented in meter passport Adoptable parameterization is performed...

Страница 50: ...crolling cycle O List of objects in main Reserved automatic data scrolling cycle O Automatic data scrolling cycle period O Manual data scrolling cycle duration O Date identification format O Decimal p...

Страница 51: ...the meter Lowest level security no security does not require any peer authentication Low Level Security LLS authentication of clients by verifying the password High Level Security HLS mutual authentic...

Страница 52: ...meterization Encryption key for Firmware update client Authentication key for Firmware update client Master key for wrapping of encryption keys and authentication keys Keys are 16 byte long write only...

Страница 53: ...d sends alarm to Central System if certain type of event is registered By default tampering events influence of magnetic field opening of terminal cover and main cover are configured for security aler...

Страница 54: ...ion Connected this state can be set by connect command from allow to connect state only Connect command can be issued from following sources o Remotely by remote control command o Local be remote cont...

Страница 55: ...register that disconnect request came from optical interface if it was received from it if command was sent from electrical interface entry is made accordingly 3 Internal state can be changed from dis...

Страница 56: ...uch principles 1 Meter measures RMS value of current every second There is configurable limit in the meter which defines the maximum value of RMS current and if this limit is exceeded an over current...

Страница 57: ...continuous voltage swing event under voltage or over voltage should go on until such event is registered protection from short term voltage swings 3 When network voltage swing event under voltage or...

Страница 58: ...corresponding message Load SET Load SET Load SET Load SET is displayed on LCD and in OBIS code area a source of disconnection is displayed Entry is made to event register that ready to connect request...

Страница 59: ...n more than 5s special timer appears on LCD meter switches to internal state connected internal relay is closed relay state LED is off corresponding message Load on Load on Load on Load on is displaye...

Страница 60: ...ort Figure 15 1 GAMA 100 connection diagram with 1 current measurement element current transformer or shunt S0 output and RS 485 interface Figure 15 2 GAMA 100 connection diagram with 2 current measur...

Страница 61: ...61 Annex A Dimensions of the meter Figure A 0 1 Dimensions of the meter and fixing holes Figure A 0 2 Dimensions of the meter with special terminal cover for GSM GPRS modem...

Страница 62: ...d in GAMA 100 meters No Name Thread Material Screw torque Nm 1 Voltage contact screw M2 5 Brass 0 32 Steel 0 43 2 Voltage link screw M3 Steel 0 76 3 Contact screw M5 Brass 2 Steel 2 7 4 Sealing bolt M...

Страница 63: ...ial number r r 1r r r r 2 0 0 1 User ID 1 user name rw 1 rw r 3 0 0 2 User ID 2 location rw 1 rw r 4 0 1 0 Billing period counter r r 3 r r 5 0 1 1 Number of entries in billing profile r r 3 r r 6 0 1...

Страница 64: ...at the end of previous billing period r r 3 r r 49 15 8 T Total energy A kWh of tariff T 1T6 current value r r 3 r r 50 15 8 T VV Total energy A kWh of tariff T 1T6 value at the end of previous billin...

Страница 65: ...r r 97 6 6 M Maximum demand Q2 kvar of tariff M 1T6 in current billing period r r 4 r r 98 6 6 M VV Maximum demand Q2 kvar of tariff M 1T6 in previous billing period r r 4 r r 99 6 8 0 Total energy R2...

Страница 66: ...r r 148 C 1 0 Meter serial number same as OBIS 0 0 0 r r 1r r r r 149 C 1 1 Meter type r r 1r r r r 150 C 1 2 Ordering code r r 1r r r r 151 C 2 0 Parameterization counter r r 3 r r 152 C 5 0 Internal...

Страница 67: ...under voltage rw 1 rw r 208 C 69 2 1 Limit values for over current in phase terminals rw 1 rw r 209 C 69 2 2 Limit values for over current in neutral rw 1 rw r 210 C 70 0 Check sum of the firmware r...

Страница 68: ...2 M Bus device settings 72 r r 255 0 2 24 2 1 2 M Bus device register 4 r r 256 0 2 24 3 1 2 M Bus device profile 7 r r 257 0 3 24 1 0 3 M Bus device settings 72 r r 258 0 3 24 2 1 3 M Bus device reg...