INSTALLATION
SINUS K
INSTRUCTIONS
136/
191
13.3.2.
O
PERATION
Each
size of the braking unit can be used with a braking resistor avoiding exceeding the max. instant current
stated in its specifications.
The braking unit is controlled directly by the control unit. Braking units cannot be parallel-connected when
applied to modular inverters.
13.3.3.
R
ATINGS
SIZE
Max. Braking
Current (A)
Mean Braking
Current (A)
Inverter Supply Voltage
Min. Braking
Resistor
(Ohm)
Dissipated
Power
(at Mean
Braking
Current)
(W)
BU1440 2-4T
1600 800 200-240Vac/ 0.24 1700
BU1440 2-4T
1600 800 380-500Vac/ 0.48 1800