83621
/ EN1503
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation
Material
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL94: V2
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2006/95/EC.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive 2011/65/EU
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27
(4R27xx)
Mounting Clip
(411884)
Read this installation guide before installing the product
83621
/ EN1503
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation
Material
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL94: V2
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2006/95/EC.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive 2011/65/EU
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27
(4R27xx)
Mounting Clip
(411884)
Read this installation guide before installing the product
83621
/ EN1503
Technical Specifications
Safety and environmental conditions
CE marking
LV directive 2006/95/EC
RoHS directive 2011/65/EU
Standard
EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following
conditions:
Location
Altitude
Ambient temperature
Storage temperature
Relative humidity
Pollution degree
Degree of protection
Indoor use
Up to 2000m
-10°C .. +55°C
-20°C .. +70°C
5% .. 85%, non condensing
2
IP20
The RM27 is only suitable for insulated primary conductors.
Specifications
Standard
Rated short-time thermal current
(Ith):
Rated dynamic current (Idyn)
Continuous thermal current (Icth)
IEC 61869-2:2012
60 x Ipr / 1s
2,5 x Ith
100%
Rated insulation level
Rated frequency
Class of insulation
Material
Secondary terminal
0,72/3/-kV
50/60Hz
E (120°C)
PA 6.6, UL94: V2
Female clamping
connector picoMAX3.5
Wago, suitable for
conductor size: 0,2 ..
1,5mm² solid, stranded
or ferruled (Strip length
8 .. 9 mm)
Specifications per type
RM27
Secondary
leads format*
0,5mm2
1,4meter
0,75mm2
2,0meter
1,0mm2
2,8meter
1,5mm2
4,0meter
Suitable for
cable
ø 7,5
Approximate
weight
40g
* Maximum length secondary leads for 0,1VA at the end of this leads.
ELEQ reserves the right to carry out modifications on its products, in
order to improve them, without prior notice.
Safety instruction
All activities for installation, commissioning and maintenance
of this current transformer must be performed by qualified
personnel that have the knowledge of applicable safety
precautions. This guide assumes that the reader of this
document has sufficient electro-technical knowledge to
understand the content of this document.
General
The RM27 is a current transformer (CT) and can only be used
measuring electrical alternating currents. The RM27 is
suitable only for mounting on insulated primary conductors in
a weather protected and dry location.
Explanation of symbols
This product is designed according to the
EN-IEC 61010-1:2010 standards and therefore this
product meets the requirements of the Low Voltage
Directive 2006/95/EC.
Read the installation guide before mounting the
product. Unprofessional work activities on electrical
installations may result in a threat of danger to the life
and health of human beings and livestock!
Under no circumstances the secondary circuit of the
CT may be opened when the CT is mounted on a
primary current and current is flowing in the primary
circuit. High voltages may appear on the
secondary leads when this circuit is left open.
RoHS Directive 2011/65/EU
ELEQ states that they only uses qualified component
in their products from manufacturers, whose
specifications meet or exceed the requirements of
the European Directive for the Restriction of use of
certain Hazardous Substances.
WEEE Directive 2012/19/EU
The 'crossed out wheeled bin' symbol indicates that
the equipment should not be disposed as unsorted
municipal waste. Contact a qualified recycler for
disposal.
RM27 Current Transformer
Installation Guide
RM27
(4R27xx)
Mounting Clip
(411884)
Read this installation guide before installing the product
ELEQ b.v.