1.8.3
Technical specifications
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value on the DC output
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 The display error adds to the error of the related actual value on the DC output
(3 For technical specifications of the analog interface see
„3.5.4.4 Analog interface specification“ on page 53
Global
AC input
Voltage (L-L)
340...460 V
AC
. 45 - 65 Hz
Connection
Three phase supply (L1, L2, L3, PE)
Fusing (internal)
Circuit breaker, 3x 32 A per unit (characteristics K)
Power factor
≈ 0.99
DC output
Temperature coefficient of the set values Δ/K
Voltage / current: 100 ppm
Voltage regulation
Accuracy
(1
(at 23 ± 5°C)
< 0.1% U
Nom
Line regulation at ±10% ΔU
AC
< 0.02% U
Nom
Load regulation at 0...100% load
< 0.05% U
Nom
Rise time 10...90% ΔU
Max. 30 ms
Transient time after load step
< 1.5 ms
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% U
Nom
Remote sensing compensation
Max. 5% U
Nom
Fall time at no load after switching DC output off Down from 100% to <60 V: less than 10 s
Current regulation
Accuracy
(1
(at 23 ± 5°C)
< 0.2% I
Nom
Line regulation at ±10% ΔU
AC
< 0.05% I
Nom
Load regulation at 0...100% ΔU
OUT
< 0.15% I
Nom
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.2% I
Nom
Power regulation
Accuracy
(1
(at 23 ± 5°C)
< 1% P
Nom
Line regulation at ±10% ΔU
AC
< 0.05% P
Nom
Load reg. at 10-90% ΔU
OUT
* ΔI
OUT
< 0.75% P
Nom
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Display: Accuracy
(4
≤ 0.4% P
Nom
Internal resistance regulation
Accuracy
(1
≤2% of max. resistance ± 0.3% of maximum current
Display: Resolution
See section
„1.9.6.4. Resolution of the displayed values“
Analog interface
(3
Set value inputs
U, I, P, R
Actual value output
U, I
Control signals
DC output on/off, remote control on/off, resistance control on/off
Status signals
CV, OVP, OCP, OPP, OT, PF, DC output on/off
Galvanic isolation to the device
Max. 1500 V DC
Sample rate of inputs & outputs
500 Hz
Insulation
AC input <-> PE
2.5 kV DC
AC input <-> DC output