background image

EN

25

Date: 06-22-2018

Instruction Manual

PS 800 R Series

6.1.3  Adjust set values 1

Analogue inputs: VSEL(1) and CSEL(2)

This example shows how the set values can be 

adjusted using the reference voltage (10V, VREF) 

and potentiometers on the set value inputs.
The bridge between pin 10 and Pin 7 switches the 

device to the required remote control mode. This 

bridge can be substituted by a low resistive switch.
In case only one of both set values shall be adjusted, 

the other one should be tied to pin VREF.

The potentiometer should be 10kΩ each or higher.

6.1.4  Adjust set values 2

Analogue inputs: VSEL(1) and CSEL(2)

The example shows how to control voltage and 

current by means of external voltage sources. Also 

see example 1.

Attention!

 Never connect voltages >12V to these 

inputs!
Set values >10V are internally clipped to 100% 

nominal value.Other applications

7.  Other applications

7.1  Series connection

It is possible to connect multiple units of preferrably 

the same type to a series connection if these rules 

are followed:

•  No master-slave operation
•  The grounds of the analogue interfaces MUST 

NOT be connected to each other. This also applies 

for any other signal on the analogue interfaces. If 

remote control is required, it can be done using 

galvanic isolation amplifiers and by controlling on 

or all units in parallel.

•  The remote sense terminal must not be wired!
•  The Share Bus terminal must not be wired!

•  No negative DC output pole of any device may 

have a potential >300V against earth (PE).

7.2  Parallel connection

The parallel connection and operation of multiple 

identical units is basically possible, but not explici-

tely supported. Due to the overvoltage protection 

level that follows the adjusted output voltage, it is 

not possible to use the analog interface to create a 

master-slave-like system or to use the Share Bus 

for load current distribution.

Applications

Содержание PS 800 R Series

Страница 1: ...PS 800 R 5000W DC Power Supply Operating Guide EA PS 880 170R 21 540 122 EA PS 8200 70R 21 540 124 EA PS 8500 30R 21 540 123...

Страница 2: ......

Страница 3: ...N 3 PS 800 R 06 22 2018 60 VDC Elektro Automatik GmbH Co KG Helmholtzstrasse 31 37 41747 Viersen Germany 49 2162 37850 49 2162 16230 www elektroautomatik cn ea1974 elektroautomatik cn Elektro Automati...

Страница 4: ...1 5 1 2 5 1 3 5 2 5 2 1 5 2 2 5 2 3 5 2 4 6 2 5 6 3 6 3 1 Remote sense 6 3 2 OVP 6 3 3 OT 6 3 4 6 3 5 6 3 6 6 3 7 6 4 7 4 1 8 5 11 5 1 11 5 2 11 5 3 11 5 4 11 6 11 6 1 11 6 1 1 11 6 1 2 11 6 1 3 1 12...

Страница 5: ...R 06 22 2018 1 1 1 PS 800 R 1 3 OVP OT 400V 1 2 1 3 1 x 1 x 2 x 2 Phoenix 2 x 4 Phoenix 2 2 1 15cm 4 11 2 2 340V 460VAC 50Hz 60Hz Power Input 3 L1 L2 PE 400V 120 5x20mm 2 3 2 5mm DC DC DC 80V 200V M8...

Страница 6: ...00 R 06 22 2018 2 4 PLC 12 0 1mm 26 AWG 0 5mm 20 AWG 2 5 Phoenix Sense 3 3 1 Remote sense 4 3 2 OVP 80V 7V 200V 17V 500V 42V 5000V OVP 217V OVP OVP 9 OV 3 3 OT OT LED 9 OT OVP 3 4 12 6 3 5 3 6 5000W P...

Страница 7: ...rms 0 2 0 2 0 2 10mV 100mV 100mV 2 5V 6V 10V INom 170A 70A 30A 0 INom 0 INom 0 INom 10 UIN 0 05 0 05 0 05 0 100 UOUT 0 15 0 15 0 15 BWL 20MHz 40mArms 11mArms 8mArms 0 2 0 2 0 2 100mA 10mA 10mA 10 90 2...

Страница 8: ...CN 8 PS 800 R 06 22 2018 4 1 4 1...

Страница 9: ...CN 9 PS 800 R 06 22 2018 3 2 500V...

Страница 10: ...CN 10 PS 800 R 06 22 2018 4...

Страница 11: ...06 22 2018 4 1 5 5 1 5 2 1 3 4 Output adjust 10 10 5 3 OVP OT Output On Off Rem SB 8 Rem SB Output On Off CC 0V 60s 5 4 Output Voltage Range 6 VSEL CSEL 0 10V 0 10V VMON CMON Remote Remote 7 VREF 10V...

Страница 12: ...Remote DI Low ULow 1V High UHigh 4V 8 Rem SB DI Low ULow 1V High UHigh 4V 9 OT OVP DO OT OVP Low ULow 1V High UHigh 4V Umax 30V Imax 20mA 15V 10 DGND 11 Reserved X 12 Reserved X 1 AO DI TTL CMOS DO T...

Страница 13: ...CN 13 PS 800 R 06 22 2018 6 1 3 1 VSEL 1 CSEL 2 10V VREF 7 10 VREF 10k 6 1 4 2 VSEL 1 CSEL 2 1 12V 10V 100...

Страница 14: ......

Страница 15: ...of electrical current Any connection between the load and the unit at the output terminals have to be scoop proof Applications connected to the power output must be configured and fused in a way that...

Страница 16: ...ertemperature OT 18 3 4 Analogue interface 18 3 5 Current limitation 18 3 6 Flexible power limitation 18 3 7 Share bus connection 18 4 Technical specifications 19 4 1 Views 20 5 Operation 23 5 1 Power...

Страница 17: ...ws unimpeded air flow through the ventilation slots Take care for plenty of space at least 15cm below and above the device in order to ensure proper cooling For the installation dimensions see section...

Страница 18: ...around 217V Because the offset is not adjustable the user has to consider possible voltage incrementals coming from the power supply before the OVP reacts In case of an overvoltage condition whether c...

Страница 19: ...y at 0 100 UOUT 0 15 0 15 0 15 Ripple BWL 20MHz 40mArms 11mArms 8mArms Accuracy 0 2 0 2 0 2 Resolution of display 100mA 10mA 10mA Transient recovery time 10 90 load 2ms 2ms 2ms Output Power Nominal po...

Страница 20: ...the device 4 1 Views Figure 1 Front view Figure 1 shows the 80V model specific DC output terminal and cover Other models use different output terminals and cover which are of bigger dimensions See 4...

Страница 21: ...21 Date 06 22 2018 Instruction Manual PS 800 R Series About the device Figure 3 Bottom view with AC input and fuseholders Figure 2 Top view with DC output here 500V model and Share bus Sense Front Fro...

Страница 22: ...EN 22 Instruction Manual PS 800 R Series Date 06 22 2018 About the device Figure 4 Side view...

Страница 23: ...hen on again Attention The pin REM SB overrides the pushbut ton Output On Off When the output is switched on the LED CC will indicate constant current operation LED is on or constant voltage operation...

Страница 24: ...t be connected 1 AO Analogue output DI digital input no TTL CMOS DO digital output no TTL CMOS Accuracy 0 2 at Imax 2mA Short circuit proof against AGND Umax 30V Iout 1mA at 5V Iout 2mA typ at 0V Accu...

Страница 25: ...Other applications 7 Other applications 7 1 Series connection It is possible to connect multiple units of preferrably the same type to a series connection if these rules are followed No master slave...

Страница 26: ......

Страница 27: ......

Страница 28: ...EA Elektro Automatik GmbH Co KG Development Production Sales Helmholtzstra e 31 37 41747 Viersen Germany Tel 49 2162 37 85 0 Fax 49 2162 16 230 ea1974 elektroautomatik cn www elektroautomatik cn...

Отзывы: