Page 59
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
PSI 9000 2U Series
Alarm Meaning
Description
Indication
OT
O
ver
T
em-
perature
Triggers an alarm if the internal temperature exceeds a certain limit. The
DC output will be switched off.
Display, analog
IF, digital IF
► How to configure the device alarms
1.
Tap the touch area
on the main screen.
2.
On the right side tap the white arrow to select “
2. Protect
”.
3.
Set the limits for the equipment alarm relevant to your application if the default value of 110% is unsuitable.
The set values can be entered using the ten-key tab. This will appear by tapping the touch area
that shows the rotary knob assignments.
The user also has the possibility of selecting whether an additional acoustic signal will be sounded if an alarm or
user defined event occurs.
► How to configure the alarm sound (also see “
„3.3.3. Configuration via MENU“
1.
Tap the touch area
on the main screen
2.
In the menu page, tap “
HMI Settings”
3.
In the following menu page, tap “
Alarm Sound”
4.
In the settings page select “
Sound on
“ or “
Sound off
” and confirm with
.
3.5.2.1
User defined events
The monitoring functions of the device can be configured for user defined events. Default is that this is deactivated
(action = NONE). The following events can be configured independently and can, in each case, trigger the actions
NONE, SIGNAL, WARNING or ALARM.
Event
Meaning
Description
Range
UVD
U
nder
V
oltage
D
etection Triggers an event if the output voltage falls below the
defined threshold.
0 V...U
Nom
OVD
O
ver
V
oltage
D
etection
Triggers an event if the output voltage exceeds the de-
fined threshold.
0 V...U
Nom
UCD
U
nder
C
urrent
D
etection Triggers an event if the output current falls below the
defined threshold.
0 A...I
Nom
OCD
O
ver
C
urrent
D
etection
Triggers an event if the output current exceeds the de-
fined threshold.
0 A...I
Nom
OPD
O
ver
P
ower
D
etection
Triggers an event if the output power exceeds the de-
fined threshold.
0 W...P
Nom
These events should not be confused with alarms such as OT and OVP which are for device
protection. User defined events can, however, if set to action ALARM, switch off the DC output
and thus protect the load, like a sensitive electronic application.
► How to configure user defined events
1.
Tap the touch area
on the main screen..
2.
On the right side tap the white arrows
to select “
4.1 Event U
” or “
4.2 Event I
” or
“
4.3 Event P
”.
3.
Set the monitoring limits with the left hand rotary knob and the triggered action with the right hand knob
relevant to the application (also see
).
4.
Accept the settings with
.