Table 4 (B2, C and correction factors for cable grouping)
B2
E
E
Number of cables
Seated in Cable Duct
Wall fixing or Cable trough
Cable tray
1
1.00
1.00
1.00
2
0.80
0.85
0.87
4
0.65
0.75
0.78
6
0.57
0.72
0.75
9
0.50
0.70
0.73
The total current included for using Table 1 should be the maximum rated current for the machine divided by the
product of the different correction factors. Other correction factors may also be applied ; consult the cable
manufacturers.
Calculation : Example
• The machine has a rated current of 60 A.
• The ambient temperature is 45 °C ; Table 2 gives a correction factor of 0.91.
• Rubber cable insulant : Table 3 gives a correction factor of 0.92.
• The cable is fixed directly to the wall (Column C), with 2 cables side by side. Table 4 gives a correction factor of
0.85.
60 A
Total current :
_________________
= 84 A
0.91 x 0.92 x 0.85
Taking Column C in Table 1 (wall fixing), we obtain a minimum cable section of : 3 x 25 mm².
22 Electricity power supply
Prior to use, the washer-extractor should be connected to a multi-pole switch prior to the machine to facilitate in-
stallation and service operations.
Caution
The electrical installation of the machine must be undertaken by qualified personnel.
Caution
Ensure that the electrical voltage is correct and that the power of your supply is sufficient, before connecting the
machine.
Caution
The main switch is located on the right side of the machine , identified by this sticker.
Note!
Содержание WH5-WHB5 500H
Страница 1: ...Installation manual Washer extractors WH5 WHB5 500H WS5 WSB5 500H original instructions 05201135 EN ...
Страница 2: ......
Страница 26: ...26 Installation manual Back view Right view Drain connection Top view ...
Страница 28: ...28 Installation manual Back view Right view Drain connection Top view ...
Страница 40: ...40 Installation manual ...
Страница 57: ...Installation manual 57 Connect cable W5 to gas boiler on connector X W5 ...
Страница 66: ...66 Installation manual ...
Страница 69: ......
Страница 70: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...