Installation manual
21
5.2
Fresh air
For maximum efficiency and the shortest possible drying time, it is important to ensure that fresh air is able to enter
the room from the outside in the same volume as that is blown out of the room.
To avoid draught in the room it is important to place the air inlet behind the machine.
The area of the air inlet opening is recommended to be five times the size of the exhaust pipe area. The area of the
inlet opening is the area through which the air can flow without resistance from the grating/slatted cover.
5 x A
A
fig.W00051
Note!
Gratings/slatted covers often block half of the total fresh air vent area. Remember to take this into account.
5.3
Exhaust duct
• Only rigid or flexible metal duct should be used for exhausting.
• Plastic ducting is not to be used.
• Recommended material for exhaust is galvanized steel.
• The duct is not to be assembled with screws or other fastening means that extend into the duct and catch lint.
• The exhaust air should not be vented into a wall, a ceiling, or a concealed space of building.
• The exhaust duct must lead clear of the building as condensation may cause frost damage to the building.
• The exhaust duct must lead to the outdoors.
• The exhaust duct must be placed in such a way that it is protected on the outside.
• The exhaust duct must be smooth on the inside (low air resistance).
• The exhaust duct must have gentle bends.
Содержание Lagoon TD6-14
Страница 2: ......
Страница 4: ...Contents The manufacturer reserves the right to make changes to design and component specifications ...
Страница 24: ...24 Installation manual Demount the lower side panel 3x fig X00979E Disconnect the NTC sensor fig X01226B ...
Страница 50: ......
Страница 51: ......
Страница 52: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...