SG1000RA general description (‘R’ is for ‘relays’)

The SG1000RA is a SlideGate Monitor with a 2-Relay output. 

The SG1000RA is a rugged, medium cost encoder-based 

monitoring device that enables the end-user to very accurately 

monitor a slide-gate’s fully-open and fully-closed positions. 

The SG1000RA has two modes: Calibration Mode, and Normal 

Operating Mode. A simple calibration procedure teaches 

(programs) the SG1000RA the fully-closed (0% open)

and fully-open (100% open) gate positions. Once programmed, 

the SG1000RA de-energizes one relay when the gate is in the 

fully-closed position, and de-energizes the other relay when the 

gate is in the fully-open position. Any gate position between 

fully-closed and fully-open, is represented by both relays being 

energized.

Physical Appearance and Installation Overview 

Figure 1 is the front-view of the SG1000RA, showing the 

encoder-output-shaft (with the most common shaft end-thread 

type shown).

Encoder-Shaft
3/8"-16 UNC-2A threads

Cable

Figure 1:

The SG1000RA attaches to the slide-gate’s ‘rack and pinion’ 

shaft, or similar rotating mechanical component, using an “end-

of-shaft” mounting method.  See Figure 2.  In the most common 

application, the SG1000RA’s encoder-shaft-end screws into a 

single 3/8-inch diameter hole, to a depth of 0.625 inch, having 

3/8” – 16 UNC-2B threads. (Other encoder-shaft end-thread 

types are optional.) 

Even though the SG1000RA is mounted to the process shaft 

via the “end-of-shaft” mounting method, installation of flexible 

conduit and of the optional stabilizer bracket is recommended, 

which allows the SG1000RA to “float” along with any wobble 

of the process’s shaft while still preventing the SG1000RA itself 

from rotating along with that shaft (see Fig. 2).

 Note:

  The stabilizer bracket’s U-bolt is slightly oversized  

 

 

to provide about 1/8” of slack between it and the  

 

 

SG1000RA. The U-bolt’s slack prevents it from  

 

 

rigidly clamping to the SG1000RA’s conduit port. 

 

Process Shaft 

SG1000

Stabilizer bracket 
(use is optional) 

U-Bolt

with slack

Structural Framework 

Flexible 
conduit 

Figure 2:

Electrical connections

First, remove (twist CCW) the back-end-cover from the 

SG1000RA’s red enclosure, to reveal the User Interface Board 

(see Figure 3).

0

F

E

DC

B A 9 8 7 6

5

43

2

1

RELAY 2

SW1

SW2

1

2

3

CAL

CAL

SET-POINT

RELAY 1

Red LED

100% Open

Relay

SW1 Relay

Setpoint

Selection

Red LED

0% Open

Relay

Green LEDs

Calibration

Status

SW2 Calibration Button

Figure 3: User Interface Board

Second, remove the nylon-retained metal nuts that hold the User 

Interface Board in place, to reveal the terminal block TB1 (see 

Figure 4)

Terminal Block

TB1

Earth Ground

Screw

1 2 3 4 5 6 7 8 9 10

Figure 4: Terminal Block View

SG1000RA SlideGate Monitor