2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.4: Accuracy
(For full Range specifications see 2.2: Specifications on page 2-12.)
Shark 200 Clock Accuracy: Max. +/-2 seconds per day at 25
o
C
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5 A
(Class 10) nominal unit, accuracy as follows:
Table 2:
Parameter
Accuracy
Accuracy Input Range1
Voltage L-N [V]
0.1% of reading
(69 to 480) V
Voltage L-L [V]
0.2% of reading
2
(120 to 600) V
Current Phase [A]
0.1% of reading
1, 3
(0.15 to 5) A
Current Neutral (calcu-
lated) [A]
2% of Full Scale
1
(0.15 to 5) A @ (45 to 65)
Hz
Active Power Total [W]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Active Energy Total [Wh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Reactive Power Total
[VAR]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Reactive Energy Total
[VARh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Apparent Power Total
[VA]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Apparent Energy Total
[VAh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Power Factor
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Frequency [Hz]
+/- 0.007 Hz
(45 to 65) Hz
Total Harmonic Distortion
[%]
+/- 2%
1, 4
(0.5 to 10) A or (69 to
480) V, measurement
range (1 to 99.99)%