Doc
#
E154713
2-19
2: Nexus
®
1500+ Meter Overview
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.7: Accuracy
1 – U
m
(measured value), U
nom
(nominal voltage range).
2 - U
din
(declared input voltage): value obtained from the declared supply voltage by a transducer ratio.
Parameters
Accuracy*
Range
Voltage
0.05% (1 s readings)
0.1% (100 ms readings)
(5 to 347) V AC L-N
(10 to 600) V AC L-L
Current
0.025% (1 s)
0.1% (100 ms)
Class 2: Nominal 1 A, maximum 2 A
Class 20: Nominal 5 A, maximum 20 A
Energy
kWh 0.06% (1 s)
kVAh 0.08% (1 s
kVARh 0.08% (1 s)
Power
kW (Unity PF) 0.1% (100 ms)
0.06% (1 s)
kW (0.5 PF) 0.1% (100 ms)
0.1% (1 s)
kVA 0.1% (100 ms)
0.08% (1 s)
kVAR (0.5 - 0.9 PF) 0.1% (100 ms)
0.08% (1 s)
Power Factor
0.1% (100 ms)
0.08% (1 s)
Frequency
0.001 Hz (10 s)
0.01 Hz (1 s)
0.03 Hz (2-20 cycles readings)
(45 to 69.9) Hz
Voltage/Current Unbalance
4
±0.05
0.5% to 5% u2
0.5% to 5% u0
Harmonic/Interharmonic
0.2% (1 s)
Voltage Sag/Swell
Duration
Depth
2
½ cycle
±0.1% U
din
4.97 hours maximum
10% to 150% U
din
Interruption duration
½ cycle
4.97hour maximum
Rapid voltage Change (RVC)
Duration
Umax
2
Uss
2
½ cycle
±0.1% U
din
±0.1% U
din
4.97 hours maximum
10% to 150% U
din
10% to 150% U
din
Mains Signaling voltage
1,3
±5% U
m
U
m
≥
1% U
nom
±0.05% U
nom
U
m
< 1% U
nom
10% to 200% of Class 3 electromagnetic
environment in IEC 61000-2-4
Flicker
0.2% to 12.5%
Temperature
(-20 to +70)
0
C
Real time clock
3.5 ppm
Timestamp (IRIG sync)
100 usec
Содержание Shark 100T
Страница 1: ...V 1 04 May 15 2018 ...