5: Communication Wiring
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The High Speed Inputs can be used with either dry or wet field contacts. For wet
contacts, the common rides on a unit-generated Nominal 15VDC. No user program-
ming is necessary to use either wet or dry field contacts.
Figure 5.8: High-Speed Inputs Connection
5.10: IRIG-B Connections
IRIG-B is a standard time code format that synchronizes event time-stamping to
within 1 millisecond. An IRIG-B signal-generating device connected to the GPS
satellite system synchronizes Nexus® 1500+ meters located at different geographic
locations. Nexus® meters use an un-modulated signal from a satellite-controlled
clock (such as Arbiter 1093B). For details on installation, refer to the User’s manual
for the satellite-controlled clock in use. Below are installation steps and tips to help
you.
Connection:
Connect the (+) terminal of the Nexus® meter to the (+) terminal of the signal
generating device; connect the (-) terminal of the Nexus® meter to the (-) terminal
of the signal generating device.
Installation
:
Set Time Settings for the meter being installed.
1. From the Communicator EXT
TM
Device Profile menu:
a. Click
General Settings>Time Settings>one of the Time Settings lines
to open the Time Settings screen.