Pag. 125 di 152
Tariff Maximum Demands Service - Output variables
Name
ID
Type
Mandat.
6
Description
MD P imp
0880h
DOUBLEWORD (ID 02h)
YES
Maximum Demand
Import Active Power
MD Q ind imp
0881h
DOUBLEWORD (ID 02h)
YES
Maximum Demand
Import Reactive power (inductive)
MD Q cap imp
0882h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Import Reactive power (capacitive)
MD S imp
0883h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Import Apparent power
MD P exp
0884h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Export Active Power
MD Q ind exp
0885h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Export Reactive power (inductive)
MD Q cap exp
0886h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Export Reactive power (capacitive)
MD S exp
0887h DOUBLEWORD
(ID
02h)
YES
Maximum Demand
Export Apparent power
The service configuration parameters are stored in the following input variables:
Tariff Maximum Demands Service – Input variables
Name
ID
Type
Range Default
Unit
Description
Max data-file size
FF00h
DWORD (ID 02h)
Unsigned integer
-
All space
available
on disk
bytes
Maximum admitted size
for each data file
Refresh Period
0800h
WORD (ID 01h)
Unsigned integer
0..65535
0
s
Refresh interval of the report file.
When not specified, it refreshes at
each time band changeover or
whenever the serial port requires a file
reading.
10.6.2 Reset
The content of a report file may be reset by simply removing the file.
This operation will generate a temporary service stall of few tenths of sec.; after checking and validation of
the configuration files a new report file will be generated.
Содержание X3M
Страница 142: ...Pag 142 di 152 ...
Страница 145: ...Pag 145 di 152 ...
Страница 151: ...Pag 151 di 152 ...